iS7 Ethernet Option Manual
8
8.
Ethernet Option and Related Keypad Parameters
The functions below are the inverter parameters which shows the
information related with the Modbus TCP and Ethernet IP. In the parameter
column, the “M” stands for the parameters used for Modbus TCP, and “E”
stands for the parameters used for Ethernet IP.
Related keypad parameter with iS7 Ethernet
Code
Number Parameter Name Default
Set
value
Description
Pro-
tocol
CNF-30
Option-1 Type
-
-
Indicates name of the
communication card installed in
the inverter (Ethernet).
M/E
COM-06
FBus S/W Ver
-
-
Indicates version of the
communication card installed in
the inverter.
M/E
COM-09
FBus Led
-
-
Shows the ON/OFF data of the
LED on the Ethernet
communication card.
M/E
COM-10
Opt Parameter1
0x0000
0x0000
~0xFFFF
Sets up the IP Address.
M/E
COM-11
Opt Parameter2
0x0000
0x0000
~0xFFFF
COM-12
Opt Parameter3
0x0000
0x0000
~0xFFFF
Sets up the Subnet Mask.
M/E
COM-13
Opt Parameter4
0x0000
0x0000
~0xFFFF
COM-14
Opt Parameter5
0x0000
0x0000
~0xFFFF
Sets up the Gateway Address.
M/E
COM-15
Opt Parameter6
0x0000
0x0000
~0xFFFF
COM-16
Opt Parameter7
0
0~2
Sets up the Ethernet
communication rate.
M/E
COM-17 Opt Parameter8
(Note1)
0
0~11
CIP Input Instance
E
COM-18 Opt Parameter9
(Note1)
0
0~11
CIP Output Instance
E
COM-30
ParaStatus Num
3
0~8
Automatically set up according to
the CIP Input Instance.
E
COM-31
Para Status-1
0x000A
0x0000
~0xFFFF
Sets up the inverter data address
which will be read by the client.
E
COM-32
Para Status-2
0x000D
0x0000
~0xFFFF
Sets up the inverter data address
which will be read by the client.
E