445
Table of Functions
Func
tio
n
Table
13.15
User/Macro Mode
–
Draw Operation Function
Group
MC1
U&M
MC1
No. LCD Display
Name
Setting Range Initial Value
Page
00 Jump Code
Jump code
0
–
99
1
-
01 Acc Time
Acceleration time
0
–
600 (sec)
Below 75 kW 20
Above 90 kW 60
02 Dec Time
Deceleration time
0
–
600 (sec)
Below 75 kW 30
Above 90 kW 90
03 Cmd Source
Command source
0
–
5
1:Fx/Rx-1
04 Freq Ref Src
Frequency reference source
0
–
9
2:V1
05 Control Mode
Control mode
0
–
5
0:V/F
06 Aux Ref Src
Auxiliary reference source
0
–
4
2:I1
07 Aux Calc Type
Auxiliary calculation type
0
–
7
0
08 Aux Ref Gain
Auxiliary reference gain
-200
–
200 (%)
100.0
09 V1 Polarity
V1 input polarity selection
0
–
1
0:Unipolar
10 V1 Filter
V1 input filter time constant
0
–
10000 (ms)
10
11 V1 Volt x1
V1 minimum input voltage
0
–
10 (V)
0.00
12 V1 Perc y1
Output at V1 minimum voltage (%)
0
–
100 (%)
0.00
13 V1 Volt x2
V1 maximum input voltage
0
–
10 (V)
10.00
14 V1 Perc y2
Output at V1 maximum voltage (%)
0
–
100 (%)
100.00
15 V1
–Volt x1’
V1
–
minimum input voltage
-10
–
0 (V)
0.00
16 V1
–Perc y1’
Output at V1
–
minimum voltage (%) -100
–
0 (%)
0.00
17 V1
–Volt x2’
V1
–
maximum input voltage
-10
–
0 (V)
-10.00
18 V1
–
Perc y2
Output at V1
–
maximum voltage (%) -100
–
0 (%)
-100.00
19 V1 Inverting
Rotation direction change
0
–
1
0:No
20 I1 Monitor(mA)
I1 input amount display
0
–
20 (mA)
0.00
21 I1 Polarity
I1 polarity display
0
–
1
0
22 I1 Filter
I1 input filter time constant
0
–
10000 (ms)
10
23 I1 Curr x1
I1 minimum input current
0
–
20 (mA)
4.00
24 I1 Perc y1
Output at I1 minimum current (%)
0
–
100 (%)
0.00
25 I1 Curr x2
I1 maximum input current
4
–
20 (mA)
20.00
26 I1 Perc y2
Output at I1 maximum current (%)
0
–
100 (%)
100.00
27
I1 Curr x1’
I1
–
minimum input current
-20
–
0 (mA)
0.00
28
I1 Perc y1’
Output at I1 - minimum current (%)
-100
–
0 (%)
0.00
29
I1 Curr x2’
I1
–
maximum input current
-20
–
0 (mA)
-20.00
30
I1 Perc y2’
Output at I1 maximum current (%)
-100
–
0 (%)
-100.00
31 I1 Inverting
Rotation direction change
0
–
1
0:No
32 P1 Define
P1 terminal function setting
0
–
48
0:FX
33 P2 Define
P2 terminal function setting
0
–
48
1:RX
34 P3 Define
P3 terminal function setting
0
–
48
5:BX
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...