Learning Advanced Features
Adv
anc
ed
Feat
ur
es
271
8.32
Easy Start
Run Easy Start to easily set up the basic motor parameters required to operate a motor in a
batch. Set CNF-
61 (Easy Start On) to “1
(Yes)” to activate the feature, initialize all parameters by
setting CNF-40
(Parameter Init) to “1 (All Grp)”, and restart the inverter to activate Easy Start.
Group Code Name
LCD Display
Parameter Setting
Setting Range
Unit
CNF
61
Parameter easy
start settings
Easy Start On 1 Yes
-
-
Easy Start Setting Details
Code
Description
CNF-61 Easy Start On
Follow the procedures listed below to set the Easy Start parameters.
No Procedures
1
Set CNF-
61 (Easy Start On) to “1 (Yes)”.
2
Set CNF-40 (Parameter Init) to
“1 (All Grp)” to initialize all parameters
in the inverter.
3
Restarting the inverter will activate Easy Start. Set the values in the
following screens on the keypad. To exit Easy Start, press the [ESC]
key.
Start Easy Set: Select “Yes”.
CNF-01 Language Sel: Select a language.
DRV-30 kW/HP Select : select the capacity of the unit.
DRV-14 Motor Capacity: Set motor capacity.
BAS-11 Pole Number: Set motor pole number.
BAS-15 Rated Volt: Set motor rated voltage.
BAS-10 60/50 Hz Sel: Set motor rated frequency.
BAS-19 AC Input Volt: Set input voltage.
DRV-06 Cmd Source: Set command source.
DRV-01 Cmd Frequency: Set frequency reference.
When the settings are complete, the minimum parameter settings
on the motor have been made. The keypad will return to a
monitoring display. Now the motor can be operated with the
command source set at DRV-06.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...