Basic Functions
160
7.5.4
RS-485 Communication as a Command Input Device
Internal RS-485 communication can be selected as a command input device by setting DRV-06
(command source) in the Drive group to “3 (Int 485)”. This configu
ration uses upper level
controllers, such as PCs or PLCs, to control the inverter by transmitting and receiving signals via
the S+, S-, and RS-485 signal input terminals at the terminal block. For more details, refer to
Group Code Name
LCD Display
Parameter Setting Setting Range Unit
DRV
06
Command source
Cmd Source
3 Int 485
0
–
5
-
COM
04
Integrated
communication
inverter ID
Int485 St ID
1
1
–
250
-
05
Integrated
communication
protocol
Int485 Proto
0 ModBus RTU -
-
06
Integrated
communication speed
Int485 BaudR
3 9600 bps
1200
–
38400
bps
07
Integrated
communication frame
setup
Int485 Mode
0 D8 / PN / S1 -
-
7.6
Local/Remote Mode Switching
Local/remote mode switching is useful for checking the inverter's operation, or to perform an
inspection while retaining all parameter values. Also, in an emergency, it can also be used to
override controls and operate the system manually using the keypad.
The [MULTI] key is a programmable key that can be configured to carry out multiple functions.
Use local/remote operation mode switching only when it is necessary. Improper mode switching
may interrupt the inverter
’
s operation.
Summary of Contents for SV-iS7 Series
Page 17: ......
Page 114: ...Peripheral Devices 97 Group 2 ...
Page 115: ...Peripheral Devices 98 Group 3 ...
Page 116: ...Peripheral Devices 99 Group 4 ...
Page 159: ...Basic Functions 142 Code Description V1 Quantizing ...
Page 465: ...Safety Funtion STO Safe Torque Off 448 14 2 1 Safety Function Wiring Diagram ...