6.6.8 Motor output voltage control (CON_57)
When the input power and rated motor voltage are different, enter the voltage
displayed on the motor’s nameplate to configure the motor voltage. The
configured voltage value becomes the output voltage for the base frequency.
If the frequency is higher than the base frequency and the input voltage is higher
than the parameter setting, the inverter regulates it and supplies the rated
voltage to the motor. However, if the frequency is higher than the base frequency
and the input voltage is lower than the rated motor voltage, the inverter supplies
the input voltage to the motor.