T_steady: Constant speed operation time at set frequency
•
T_dec: Deceleration time to a frequency lower than constant speed
operation or the stop time from constant speed operation frequency
•
T_stop: Stop time until operation resumes
Do not set the braking resistor to exceed the resistor’s power rating. If overloaded; it can
overheat and cause a fire. When using a resistor with a heat sensor, the sensor output can be
used as an external trip signal for the inverter’s multi-function input.
6.2.6 Low Battery Voltage Warning
The H100 series has a battery low voltage warning feature. If the low battery voltage
warning function is set to ‘Yes,’ a low battery voltage warning occurs when the battery
voltage is lower than 2 V (normal voltage is 3 V). Replace the battery when the low battery
warning is displayed.
Group
Code
Name
LCD Display Parameter Setting Setting Range
Unit
PRT
90
Low battery
voltage detection
Low Battery 0
None
0
None
-
1
Warning
Low Battery Voltage Warning Detail Settings
Code
Description
PRT-90 Low Battery
The low battery voltage warning for RTC function installed in the
inverter can be enabled or disabled. The low battery voltage warning
occurs when the battery voltage is lower than 2 V.
•
Be careful when replacing the battery. Remaining voltage in the battery may cause electric
shock.
•
Make sure that the battery doesn’t fall inside of the inverter.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...