Protection Features
309
Electronic Thermal (ETH) Prevention Function Setting Details
6.1.2 Motor Over Heat Sensor
To operate the motor overheat protection, connect the overheat protection temperature
sensor (PT 100, PTC) installed in the motor to the inverter’s analog input terminal.
Group Code Name
LCD Display
Parameter
Setting
Setting
Range
Unit
PRT
34
Selecting the operation
after the detection of the
motor overheat detection
sensor
Thermal-T
Sel
0
None
0
–1
-
35
Selecting the input of the
motor overheat detection
sensor
Thermal In
Src
0
Thermal In 0
–1
36
Fault level of the motor
overheat detection sensor
Thermal-T
Lev
50.0
0.0
–100.0 %
37
Fault area of the motor
overheat detection sensor
Thermal-T
Area
0
Low
0
–1
OUT
07
Analog output 2 item
AO2 Mode
14 Constant
0
–18
08
Analog output 2 gain
AO2 Gain
100
0
–100
%
Motor Overheat Protect Sensor Input Detail Settings
PRT-43 ETH Cont
Sets the amount of current with the ETH function activated. The range
below details the set values that can be used during continuous operation
without the protection function.
Summary of Contents for LSLV-H100 Series
Page 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Page 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Page 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Page 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Page 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Page 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Page 35: ...Installing the Inverter 22 ...
Page 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Page 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Page 181: ...168 Learning Advanced Features PID Command Block ...
Page 182: ...169 Learning Advanced Features ...
Page 183: ...170 Learning Advanced Features PID Feedback Block ...
Page 184: ...171 Learning Advanced Features PID Output Block ...
Page 185: ...172 Learning Advanced Features PID Output Mode Block ...
Page 198: ...185 Learning Advanced Features EPID1 Control block ...
Page 199: ...186 Learning Advanced Features EPID2 Control block ...
Page 220: ...207 Learning Advanced Features ...
Page 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Page 506: ...Table of Functions 493 ...
Page 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Page 549: ...Troubleshooting 536 ...
Page 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Page 570: ...Technical Specification 557 110 185 kW 3 phase ...
Page 601: ...588 ...
Page 602: ...589 ...
Page 603: ...590 ...