- Instruction Manual for ESS R050096 -
25
3.6 Hybrid Inverter Cable Connection
3.6.1 Inverter Ground Connection
Ground cable shall be connected to ground plate on grid side this prevents electric shock. If the
original protective conductor fails.
Picture 3-18 Inverter ground connection
3.6.2 Battery connection
Please follow below steps to implement battery connection:
(1)
Please choose a suitable battery cable with correct connector which can well fit into the
battery terminals. Use a suitable screwdriver to unscrew the bolts and fit the battery connectors in,
then fasten the bolt by the screwdriver, make sure the bolts are tightened with torque of 5.2 N.M.
(2)
Nm in clockwise direction, make sure polarity at both the battery and inverter is correctly
connected.
Picture 3-18 Battery connection
(3)
In case of children touch or insects go into the inverter, please make sure the inverter
connector is fasten to waterproof position by twist it clockwise.
Before making the final DC connection or closing DC breaker/disconnect, be sure positive (+)
must be connect to positive (+) and negative (-) must be connected to negative (-). Reverse polarity
connection on battery will damage the inverter.