PROTECTIVE EARTH MUST BE CONNECTED!
1 2
3 4 5
POWER1
POWER2
USB1
USB2
Ethernet1
Ethernet2 6 7 8 9 1011
RS-485 Extension
85 - 264 VAC
-
24 VDC
EIA-485
L-TERM
Termination
+
2 x USB
2 x 10/100Base-T
(RJ45)
Extension
cable
61006001
AUDIO OUT
-
+
GND
EARTH
Stereo Plug
TRS connector
Stereo 3.5 mm
0,2 - 2,5 mm
2
Weidmüller BLZP 5.08/03/180
7
GND
TEMP
+3 V
DIGIN1
GND
DIGIN0
Extension cable
Nr. 61006001
Modular
connector
6p6c (RJ12)
black GND
green TEMP
red
+3 V
white DIGIN1
blue GND
yellow DIGIN0
PE
DC only!
Connectors
POWER1
1 Power supply AC input
85-264 VAC 2 Power supply AC input
POWER2
3 Power supply DC input earth ground
24 VDC
4 Power supply DC input MINUS
5 Power supply DC input PLUS
do not connect PLUS to GND
CEA-709
6 Input earth ground
TP/FT-10
7 Input B
TP/LPT
8 Input A
EIA-485
9 Input GND
10 Input +
11 Input -
B A
CEA-709
FT/LPT
Document 88076801
2010-01
Printed in Austria
Data is subject to change
http://www.loytec.com
LOYTEC
LOYTEC electronics GmbH
MADE IN
AUSTRIA
W51/2009
LVIS-3E112
8000000350EF
8000000350F0
000AB0011D87
007902-8000000350EF
NID1
VID1
MAC1
SER#
Node ID of CEA-709 Port
Virtual (Node) ID of CEA-852 port (Ethernet)
MAC address of CEA-852 Ethernet port
Serial number of the device
Date Code
RS-485 FT CNIP
LINK
ACT
ONLINE
Ethernet2 Ethernet1
MICROSD
PC USB
RESET
STATUS
POWER
STAT
Status LEDs
FT
GREEN flashing fast
Traffic on CEA-709 port
GREEN flashing at 1 Hz CEA-709 port not commissioned
RED permanent
CEA-709 port is damaged
RED flashing fast
Traffic overload on CEA-709 port
CNIP GREEN
IP port is fully functional
YELLOW
IP port functional but config. is not up-to-date
RED
IP port is non-functional
Flashing at 1Hz
IP port not commissioned
OFF
IP port not active
LINK GREEN
Ethernet link
ACT
GREEN flashing
Ethernet traffic
ONLINE GREEN
Node is in configured online state
PWR GREEN
Power
STAT OFF
Normal operation
Buttons
RESET
Reset
STATUS Send service pin message