L-IP User Manual
128
LOYTEC
Version 6.1
LOYTEC electronics GmbH
is considered to be in overload state. Set this value to 0 to exclude the missed preamble rate
from the calculation of the overload state.
If the plug-in runs in online mode the changes can be saved in the LNS database and
downloaded to the device by pressing the “Save Settings” button, if the plug-in is in offline
mode changes are only saved in the LNS database and will be downloaded to the device the
next time the network management tool is in online mode.
Figure 126: Download configuration to second router?
If router redundancy is used and a twin router is assigned the configuration can also be
synchronized with the twin router. Simply click “Yes” in the dialog shown after the
configuration was stored for the selected router (see Figure 126). It is strongly
recommended to always keep the configuration properties in both routers identical to
guarantee smooth operation.
Default settings can be restored by pressing the “Set Defaults” button. To copy the values
currently used by the device to the LNS database press the button “Load from Device”.
9.6 Web Interface
On the L-IP Redundant an additional item “Redundant” is found in the main menu of the
web interface (see Figure 127). This menu item offers the following submenus:
9.6.1 Status
Figure 127 shows the status page. This page offers similar information as the status view of
the L-IP Redundant Plug-In (see Section 9.5.3).
Major differences compared to the plug-in interface are:
When clicking on the “Send Service Pin Message” button a service pin message is sent
by the L-IP Redundant Diagnostic node.