3.
Press the
Export Device Templ.
button. This opens the
Export Modbus Device
Template
dialog shown in Figure 195. The list on the left side of the dialog shows the
names of the data points which are exported to the template.
Figure 195 Export Modbus Device Template dialog.
4.
Press the
button and select a template file from the
Save
dialog.
5.
Enter the
Creator
,
Company
Name
and
Version
for the template. This information is
stored in the template file, when importing the template file the information is displayed
after selecting the file.
6.
Press the
Export
button.
To Create a Modbus Device Template File Using a Device Template
1.
Right-click on the folder
of the device template that has to be exported or its data point
folder and select
Export Device Template…
from the context menu.
2.
This opens the
Export Modbus Device Template
dialog as shown in Figure 195.
Proceed as described above.
11.5.5 Poll Groups
In a Modbus network, the master has to poll the slave devices. Input data points are
therefore attached to a poll group. If nothing else is specified, the default poll group is used
for input data points. The default poll group has a poll cycle of 60 seconds.
Two different types of poll groups can be specified:
Time-based: The poll group is triggered on a time base. This means that after a
specific time – the poll cycle – the poll group is processed.
Trigger-based: The poll group is triggered on a special trigger data point. As soon
as the trigger condition is met, the poll group is processed.
Tip:
The poll group a data point is attached to can be changed in the properties view of the
data points. The poll group can also be changed for multiple data points using multi-
select.
To Create a Time-Based Poll Group
1.
Select the Modbus dialog by clicking on the
Modbus
button