L-INX User Manual
154
LOYTEC
Version 4.0
LOYTEC electronics GmbH
Figure 135: EDE Export Dialog.
3.
Click the
button to select the EDE file export location.
4.
Specify the
Device Name
and
Device Instance
. The device instance will be used by
other tools to configure their BACnet clients for accessing the exported device.
5.
Optionally fill in project name, author to document that information in the EDE file.
6.
Click
Export
.
6.9.7 Map other Properties than Present_Value
When creating a BACnet server object, the Present_Value property is mapped by the
created data point. That means writing and reading on the data point reads or writes the
Present_Value. If other properties shall be accessed, they must be added to the BACnet
server object‘s data point.
To Add other Properties
1.
Select the BACnet server object for adding properties.
2.
Right-click on the data point and select Add/Remove BACnet properties … . The
dialog appears as shown in Figure 136.
Figure 136: Dialog for adding/removing BACnet properties.
3.
Check the additional properties. Checking the
Read
box will add an input data point,
checking the
Write
box will add an output data point.