L-INX User Manual
120
LOYTEC
Version 4.0
LOYTEC electronics GmbH
Start the Configurator stand-alone
Section 6.6.1
Restore a backup file to the device
Section 6.6.6
START
DONE
Replace the device in LNS
Section 6.4.7
Figure 94: Basic work flow to configure a replacement device.
Start the Configurator software stand-alone and connect via the FTP method (see Section
6.6.1). Then restore the device configuration from the backup file, which has been created
when the original device has been configured or modified (see Section 6.6.6). After the
restore all data points, dynamic NVs and bindings are restored. The device is again
configured online and fully functional in the CEA-709 network.
If using an LNS-based tool, the device needs to be replaced in that tool at some later point
in time (see Section 6.4.7) as the NID has changed. If you are not using LNS, then refer to
your network management tool‘s reference manual on how to replace a device.
6.4.6 Adding the L-INX to LNS
To configure a L-INX in your LonMaker drawing, the device needs to be added to the LNS
database and commissioned. This Section refers to LonMaker TE and describes how to add
a L-INX to your database. The example discusses a LINX-10X but it is general to all CEA-
709 L-INX models
To Add a Device to LonMaker TE
1.
In your LonMaker drawing, drag a device stencil into the drawing. Enter an appropriate
name as shown in Figure 95.
Figure 95: Create a new device in the drawing.