L-INX User Manual
110
LOYTEC
Version 4.0
LOYTEC electronics GmbH
Automatically structure imported data points for faster OPC browsing
: This
option enables the automatic generation of sub-folders when using data points on the
device. A sub-folder is created for each scanned or imported device. This allows OPC
clients to browse the OPC tags in a hierarchical way.
Figure 84: General Project Settings.
6.3.2 Data Point Naming Rules
The data point naming rules tab (see Figure 85) allows specifying how data point names are
automatically derived from scanned network variables. This function is applicable to the
CEA-709 technology only. The preview shows how names would look like, when the check
marks are modified.
Use programmatic name, Use display name
: This option decides, how the data point
name is extracted from the NV. The programmatic name is the NV name from the XIF
file. The display name may be extracted from LNS, which allows to display a different
name than the programmatic name.
Figure 85: Data Point Naming Rules Project Settings.
6.3.3 CEA-709 Settings
The CEA-709 configuration tab as shown in Figure 86 allows configuring properties of the
device‘s CEA-709 port. The options are:
Enable Legacy Network Management Mode
: This group box contains check boxes
for each CEA-709 port of the device. Put a check mark on the port, if this port shall be
operated in the legacy network management mode. In that mode, the port does not use
the extended command set (ECS) of network management commands. This can be