L-DALI User Manual
82
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Delete
: Delete the selected device(s) from the data base. This clears the
assignment to a L
ON
M
ARK
/BACnet object, the group assignment, and the device
name. Further, it resets the DALI device to factory defaults.
Unassign
: Clear the assignment to a L
ON
M
ARK
/BAC
NET
object, but keep the
group assignment and the device name.
Wink
: Wink the selected devices.
On
: Switch the selected devices on (applies only to lamps).
Off
: Switch the selected devices off (applies only to lamps).
Reset Run Hour
s: Reset the run hours of the selected lamps (applies only to
lamps).
Reset Energy Count
: Reset the run hours of the selected lamps (applies only to
lamps).
Start Burn-In
: Start the burn-in mode. Some lamps require a burn-in time during
which they must not be dimmed. The burn-in time is defined by the configuration
property
nciBurnInTime
(L
ON
M
ARK
) or
Burn_In_Time
(BACnet) of the
corresponding channel fieldbus object. During this time the lamps will only be
switched to on (100%) or off (0%) but not dimmed. The remaining burn-in time is
displayed in the status column (see Figure 79 for an example).
Abort Burn-In
: Abort burn-in mode.
Emergency Light: Configure Test
: Configure auto-test calendar of self-
contained emergency lights. See Section for 5.3.4.7 details.
Emergency Light: Start Function Test
: Start function test of self-contained
emergency lights supporting this function. Please refer to the documentation of
the ballast vendor to determine whether the ballast supports execution of a
function test. Whether the function test is executed, pending or failed is shown in
the status of the selected devices. A test is pending if its execution is delayed as
the current state does not permit the execution of the test (e.g. battery not fully
charged, other test being performed, etc.). Test results will be stored in the
appropriate emergency light test log (see Section 8.1.4).
Figure 79: DALI Lamps in Burn-In Mode
Emergency Light: Stop Function Test
: Abort any function test currently
executed or pending.
Emergency Light: Start Duration Test
: Start duration test of self-contained
emergency lights supporting this function. Please refer to the documentation of
the ballast vendor to determine whether the ballast supports execution of a
duration test. Whether the duration test is executed, pending or failed is shown in