Lowell SEQR-8RJ Quick Start Manual Download Page 2

Lowell strives to provide accurate information while reserving the right to change specifications and/or improve manufacturing methods without prior notification.  
©2021 Lowell Manufacturing Co., 100 Integram Dr., Pacific MO 63069 / tel. 800.325.9660 / www.lowellmfg.com 

Spec 1748

Model SEQR-8RJ  Rev. 06-09-21 | pg. 2/3

INTERNAL USE 

ONL

Y:

 PN 24375

Includes power supply (attached)

ALARM SYSTEM INTERFACE:

If required by local building code, facility 

usage, or the Fire Marshal; the system 

functions can be overridden and the 

system controlled by contact closures 

provided by the fire alarm panel or other 

similarly installed device. A maintained 

contact between the ‘com’ terminal and 

any of the terminals shown will provide 

the following functions. 

CAUTION: 

 Do not allow alarm system 

to make more than one of the following 

contacts at the same time—controller 

board damage may result.

 

•   Lock  Off: 

A maintained contact 

between the ‘com’ terminal and the 

‘lock off’ terminal will turn the system 

off and keep it off regardless of other 

switch activations. If the system is 

already off, it will be kept off.

•   Lock  On:

 A maintained contact 

between the ‘com’ terminal and the 

‘lock on’ terminal will turn the system 

on and keep it on regardless of other 

switch activations. If the system is 

already on, it will be kept on.

•   Switch  Lock:

 A maintained contact 

between the ‘com’ terminal and the 

‘switch lock’ terminal will lock the 

system in its current state, either on 

or off, regardless of any other switch 

activations. 

RPC CONNECTIONS (8 steps):

Connect equipment to Lowell RPC Series 

remote power controls that feature classic 

connections (not pass-through), and connect 

the RPCs to one of the steps on the sequencer 

using wire (phoenix style terminals) or CAT5/6 

cable (RJ45 terminals). This sequencer allows 

up to 50 RPCs to be connected in parallel on 

each of the eight circuits. 

REMOTE SWITCH CONNECTIONS:

Lowell RPS Series switches with 

MOMENTARY closure can be connected 

to control the sequencer from remote 

locations. Up to 8 momentary switches 

may be connected in parallel.  

Maximum wire distances:  24-gauge 

= 20,000 ft.;  22-gauge = 31,200 ft.; 

18-gauge = 76,800 ft. 

Pins 1, 2  V+

Pins 3, 4  Switch

Pins 5, 6  ON Ind.

Pins 7, 8   OFF Ind.

Pins 1, 2

Pins 3, 4 

OF

In

d.

ON

 In

d.

Sw

itch

V+

Lock Switches

Lock ON

Lock OFF

Com

Pins 1, 2  V+

Pins 3, 4  Switch

Pins 5, 6  ON Ind.

Pins 7, 8   OFF Ind.

Pins 1, 2

Pins 3, 4 

OF

In

d.

ON

 In

d.

Sw

itch

V+

Lock Switches

Lock ON

Lock OFF

Com

Pins 1, 2  V+

Pins 3, 4  Switch

Pins 5, 6  ON Ind.

Pins 7, 8   OFF Ind.

Pins 1, 2

Pins 3, 4 

OF

In

d.

ON

 In

d.

Sw

itch

V+

Lock Switches

Lock ON

Lock OFF

Com

Off  On

Off  On

Use CAT5/6 cable for 

RPS Series MOMENTARY 

switch that has two LEDs 

and an RJ45 jack. 

RPC Series remote 

power controls use 

two (2) connectors

RPC Series remote power 

controls with an RJ45 

jack use CAT5/6 cable*

*Not for use with RPCs that 

feature pass-through RJ45 

jacks

Use four (4) connectors for 

RPS Series MOMENTARY 

switch that has two LEDs.

Use three (3) connectors for 

RPS Series MOMENTARY 

switch that has one LED.

Nor

m

Test

Nor

m

Test

NOTE:  Use only “straight-through” 

type RJ45 cables (pin 1 to pin 1,  

pin 2 to pin 2, pin 3 to pin 3, etc.)