Storage

 

 

1. First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables con-   

 

nected to the UPS to avoid battery drain. 

 

2. The UPS should be stored in a cool dry location.

 

3. Make sure the battery is fully charged before the UPS is stored.

 

4. For extended storage in moderate climates, the battery should be charged for 12 hours every 3  

 

 

months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat it    

 

every 2 months in high temperature locations.

Basic Operation

Front and Top Panel Description 

 

1. Input Circuit Breaker

 

The circuit breaker provides optimal overload protection.

 

2. AC Inlet 

 

Connect to utility power through the input power cord. 

 

(IEC320 C14 for 700VA/1000VA/1500VA, IEC 320 C20 for 2000VA)

 

3. AC outlet

 

The UPS provides outlets for connected equipment to insure temporary uninterrupted operation during    

 

a power failure and against surges and spikes.

 

4. USB Port

 

This port allows connection and communication from the USB port on the computer to the UPS unit.

 

5. Power On/Off Button

 

Press the power Button to turn the UPS ON or OFF.

 

6. Setting Button

 

The audible alarm can be turned off/on by pressing this button 3s.

 

7. LCD Display

 

The LCD will display the UPS status.

Summary of Contents for UPSV-1000

Page 1: ...Pure Sine Wave Line Interactive UPS Value Series Models UPSV 700 UPSV 1000 UPSV 1500 UPSV 2000 User Installation Manual power TM Rev 3 15 17 ...

Page 2: ...rtation 3 Preparation 3 Installation 3 Hardware Installation 3 Maintenance Service and Faults 4 Storage 5 BasicOperation 5 Front and Top Panel Description 5 LCDIndicators 6 Troubleshooting 7 Fault Reference Codes 8 Specifications 9 Shipping List 9 Obtaining Service 10 LimitedWarranty 11 ...

Page 3: ...y Hardware Installation Guide 1 Your new UPS may be used immediately upon receipt However recharging the battery for at least 8 hours is recommended to ensure that the battery s maximum charge capacity is achieved Charge loss may occur during shipping and storage To recharge the battery simply leave the unit plugged into an AC outlet The unit will charge in both the on and off position 2 With the ...

Page 4: ...circuit is not isolated from the input voltage Hazardous volt ages may occur between the battery terminals and the ground Before touching please verify that no voltage is present Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when working with batteries Remove wristwatches rings and ot...

Page 5: ... locations Basic Operation Front and Top Panel Description 1 Input Circuit Breaker The circuit breaker provides optimal overload protection 2 AC Inlet Connect to utility power through the input power cord IEC320 C14 for 700VA 1000VA 1500VA IEC 320 C20 for 2000VA 3 AC outlet The UPS provides outlets for connected equipment to insure temporary uninterrupted operation during a power failure and again...

Page 6: ...Definitions for Illuminated LCD Indicators LCD Indicators AC INPUT Voltage V OUTPUT Voltage V Initial Line mode Bat mode Battery capacity Load capacity Fault Sound disable Press the setting key 3s to disable and enable the buzzer sound ...

Page 7: ...ide power to equipment Circuit breaker is tripped due to overload Turn the UPS off and unplug at least one piece connected equipment Unplug the power cord of the UPS then press the circuit breaker knob Batteries are discharged Allow the unit to recharge for at least 4 hours Unit has been damaged by a surge or spike Contact technical support Alarm code A51 Site Fail Line and neutral conductors of U...

Page 8: ... requires more power than the UPS can provide It will shutdown Shut off non essential equipment If this solves the overload problem the UPS will transfer to normal operation Fault code E18 Fan fail Fan has been damaged 1 Shut down the UPS 2 Replace the fan Fault code E19 Over Temperature 1 Shut down the UPS Restart the UPS to Check the fan for operation and if the ventilation hole has been covered...

Page 9: ...istortion 2 100 linear load 5 100 non linear load BATTERY Battery type Sealed maintenance free lead acid Battery quantity size 1 12V 9AH 2 12V 7AH 2 12V 9AH 2 12V 9AH Charging current 1A max Typical recharge 4 hours to 90 PHYSICAL Dimensions W x D x H 17 2 x 16 1 x 3 5 Weight 24 lbs 27 3 lbs 36 5 lbs 36 5 lbs Line cord removable 6ft 5 15P to C13 6ft 5 20P to C19 Receptacles 8 NEMA 5 15R ENVIRONMEN...

Page 10: ...ion and if possible help solve the problem over the phone In the event that the unit requires factory service the representative will issue you a Return Material Authorization number RMA If you are returning the UPS for service please follow these procedures 1 PacktheUPSinitsoriginalpackaging Iftheoriginalpackagingisnolongeravailable asktheLowellrepresentative about obtaining a replacement set of ...

Page 11: ...y or a Lowell Manufacturing Company approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technica...

Reviews: