Lowell power UPS9LI-1500 User Manual Download Page 22

20 

 

 

 

5. Storage and Maintenance  

 

Operation   

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient 

temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.   

 

Storage   

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, 

recharge the battery in accordance with the following table:  

Storage Temperature  

Recharge Frequency  

Charging Duration  

35°C ~ 45°C  

Every month 

1 hour @5~35

  

25°C ~ 35°C  

Every 1-3 months  

1 hour @5~25

  

-10°C ~ 25°C  

Every 3-12 months  

1 hour @5~25

  

 

 

Summary of Contents for UPS9LI-1500

Page 1: ...Online Uninterruptible Power Supply w Lithium Battery User Manual Lowell Models UPS9LI 1500 UPS9LI 2000 UPS9LI 3000 2022 Lowell Manufacturing Company Version 1 0 8 4 22...

Page 2: ...View 3 2 2 Operating Principle 4 2 3 Install the UPS 4 2 4 Set up the UPS 5 2 5 Battery Replacement 7 3 Operations 9 3 1 Button Operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wording...

Page 3: ...tested CE marked or UL marked for 100 110 115 120 125 VAC models mains cable e g the mains cable of your computer to connect the UPS system to the building wiring outlet shockproof outlet Please use o...

Page 4: ...e skin and eyes It may be toxic Batteries may cause electric shock and have a high short circuit current Please take the precautionary measures specified below and any other measures necessary when wo...

Page 5: ...place for future use 2 1 Rear panel view NEMA Type 1 5K 2K 3K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Network Fax Modem...

Page 6: ...low steps to re connect battery wires first Remove front panel Connect the AC input and Put the front panel back re connect battery wires on the unit This UPS can be either displayed on the desk or mo...

Page 7: ...PS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords For 100 110 115 120 125 127VAC models The power cord is attached to the UPS The input p...

Page 8: ...ions Step 4 Network connection Network Fax Phone surge port Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipm...

Page 9: ...starts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is sound...

Page 10: ...8...

Page 11: ...y Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltag...

Page 12: ...equency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load Information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overloa...

Page 13: ...Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Ba...

Page 14: ...disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output frequency...

Page 15: ...120 Models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass functi...

Page 16: ...low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programm...

Page 17: ...it will activate EPO function with Pin 1 and Pin 2 in open status AC Active Close When AC is selected as EPO logic it will activate EPO function with Pin 1 and Pin 2 in close status 17 Site fault dete...

Page 18: ...ble range or power failure the UPS will backup power from battery and alarm is sounding every 5 seconds Bypass mode When input voltage is within acceptable range but UPS is overload UPS will enter byp...

Page 19: ...Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At this time UPS is off to remind users something wr...

Page 20: ...teries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28...

Page 21: ...load is no longer supplied by power Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capac...

Page 22: ...eplaced In this case please contact your dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance...

Page 23: ...ty PHYSICAL Dimensions W x D x H in 17 2 x 15 1 x 3 5 17 2 x 19 x 3 5 17 2 x 23 8 x 3 5 Weight lbs 25 6 33 5 45 2 Line cord 6 ft 5 15P 6 ft 5 20P 6 ft L5 30P Receptacles 8 NEMA 5 15R 8 NEMA 5 15 20R L...

Page 24: ...Vac input 1350VA 1040W 13 5A 100Vac input UPS9LI 2000 100 125Vac 50 60Hz 16A 1 100 110 115 120 125Vac 50 60Hz 1 2000VA 1800W 16A 125Vac input 2000VA 1800W 16 7A 120Vac input 2000VA 1740W 17 4A 115Vac...

Page 25: ...well Manufacturing Company approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limi...

Reviews: