en
– Original instructions
39
9 Technical Data
Table 16: Electrical, Environmetal and Installation specifications
e-SM Drive model
103
105
107
111
115
303
305
307
311
315
322
Input
Input frequency [Hz]
50/60 ± 2
Main supply
LN
L1 L2 L3
Nominal input voltage [V]
208÷240 ±10%
208÷240 / 380÷460 ±10%
380÷
460
±10%
Maximum current absorbed
(AC) in continuous service (S1)
[A]
See data plate
PDS Efficiency Class
IES2
Output
Min.÷Max. Speed [rpm]
800÷3600
Leakage Current [mA]
< 3,5
I/O au 15VDC power
supply [mA]
Imax < 40
Fault signal relay
1 x NO Vmax < 250 [VAC] , Imax < 2 [A]
1 x NO Vmax < 250 [VAC] , Imax < 2 [A]
Motor status relay
-
1 x NO Vmax < 250 [VAC] , Imax < 2 [A]
EMC (Electro Magnetic
Compatibility)
See Par. Declarations.
Installations must be performed in accordance with the EMC good practice
guidelines (e.g. avoid "eyebolts" on the transmission side)
Sound pressure LpA
[dB(A)] @ [rpm]
< 62 @3000
< 66 @3600
Insulation class
155 F
Protection class
IP 55, Enclosure Type 1
Protect the product from direct sunlight and rainfall
Relative humidity (storage &
operating)
5% ÷ 95% RH
Storage temperature
[°C] /[°F]
-25÷65 (-13÷149)
Operating temperature
[°C] /[°F]
-20÷50 (-4÷122)
Air Pollution
Pollution Degree 2
Installation altitude a.s.l. [m] / [ft]
< 1000 / 3280
Derating may occur at higher altitudes