Parameter Description
Compressor / Set Point Menu

SEt Sets the Ambient Temperature set point between r1 and r2
r0

Differential or hysteresis for set point
(For d0 = re)
Ambient temperature ≥ SEt + r0 

Output On

Ambient temperature ≤ SEt

Output Off

(For d0 = in)
Ambient temperature ≤ SEt - r0 

Output On

Ambient temperature ≥ SEt

Output Off

r1

Minimum value for set point

r2

Maximum value for set point

r4

Set point deviation from Set value during night setting

r6

Fan Relay Operation
On = Fan is always on while temperature < F0
Off = Fan is always off during regulation
CON = Fan is on when compressor is on

F0

Fan turns off when temperature is greater than this value.
Fan turns on when temperature is less than this value + A0

F1

Determines if fan stops when door is open
No = Fan does not stop working when door is open
Yes = Fan stops when door is open

c0

Minimum time compressor must remain off before being restarted

c1

Duration of continuous cold cycle

c2

During probe error, time that output is engaged

c3

During probe error, time that output is disengaged

c4

Minimum time compressor must stay on

c5

Minimum time between compressors starts

Defrost Menu

d0

Type of Defrosting
re = Defrosting without connecting the compressor
in = Defrosting by connecting compressor

d1

Defrosting stops when defrost probe temperature is above this value

d2

Maximum time the control will be in defrost cycle. If set to zero, control will
not defrost

d3

Hour of the day for the first defrost. No defrost cycles will take place before
this time

d4

Upon powering on the control, delay time before first defrost cycle

d5

Display during defrost cycle
Off = Current temperature displayed
On = Temperature at start of defrost cycle displayed until defrost cycle 
ends and the temperature is less than or equal to starting temperature or 
after the time is set in d6.

d6

Maximum time before the display returns to normal reading after a defrost
cycle

d7

Time after defrost cycle before the compressor can be started

d8

Time between defrost cycles. If set to 0, defrost must be manually actuated

d9

Determines if Fan operates during defrost

d10 Amount of time after defrost before the fan can restart
d11 Minimum duration the control remains in defrost cycle
d12 Determines which temperature probe to use to control the defrost cycle
d13 Selection of Intelligent Defrost Method

off = turns off intelligent defrost
JuP = Skips defrost cycles as necessary
CiC = Adjusts time of defrost cycle as necessary

d14 Units to count the defrost cycle

rt = according to the time the controller was on
ct = according to the time the compressor was on

d15 The time of the defrost cycle will not be counted if the evaporator 

temperature is above this value

d16 Sets the normal defrost time as a percentage of d2.
d17 Value that d8 will be incremented or decremented during Intelligent defrost

when d13 = CiC

Hde Hours until next defrost cycle
nde Minutes until next defrost cycle
JdF Displays the adjustments to the defrost cycle during intelligent defrost

When d13 = JuP, displays number of defrost cycles to skip
When d13 = CiC, displays increments of d8.

Display Menu

P0

Selection of Engineering Unit (F or C)

P1

Ambient Probe Calibration Adjustment

P2

Defrosting Probe Calibration Adjustment

P4

Decimal Point Present

P5

Probe to display

P6

Probe 2 Present

Alarm Menu

A0

Alarm Differential or Hysteresis

A1

High Alarm Set Point (Deviation Value)
On when temperature reaches Set + A1 and off at Set + A1 - A0

A2

Low Alarm Set Point (Deviation Value)
On when temperature reaches Set - A2 and off as Set - A2 + A0

A3

Time of Alarm Inhibit after Continuous Cool Cycle

A4

Time of Alarm Inhibit after Continuous Defrost Cycle

A6

Time of Alarm Inhibit after Power Up

A7

Time since Alarm Initiated until Validated

A8

Probe to be used for Alarm Settings

Initial Setup Menu

Hor Real Time Hours
nin

Real Time Minutes

E0

Assignment of Digital Input
Off = Digital Input disabled
A1 = External alarm condition when short circuited
In = Door open if short circuited
DEF = Defrost Cycle initiated when shirt circuited
Ndf = Defrost Cycle will be bypassed when shirt circuited
RSt = Night Set Points used when short circuited

H0

Restore Factory Configuration

H1

Assign Master/Slave for Defrost Cycles
Mst = Sends signal through digital input to initiate slave controls to start 
defrost
Slv = Performs defrost when receives defrost signal through digital input
(E0 = DEF when using master/slave operation)

H2

Keypad Password Protected
Yes = code is necessary to start/stop defrost or continuous cold cycle. 
One minute after entering the code, keypad is locked again
No = Keypad not protected

H3

Compressor delay time upon power up

H4

Address for serial communications (Need Model TS485 communication 
module)

H5

Input code to Parameters (factory set at 0)

H6

Input Probe Types: PTC or NTC

H7

Assignment for Relay 2
Lit = Light
Fan = Fan
ALA = Alarm
dEF = Defrost

H8

Assignment for Relay 3 (only available on 3 output models)
Lit = Light
Fan = Fan
ALA = Alarm
dEF = Defrost

H11 HACCP Alarm recording enabled or disabled
dAt Real Time Date can be programmed by holding the set key for 3 seconds.

Then, use arrows to select day. Press set to store day; use arrows to 
access month and year

td

The display refreshes at 1 degree if actual temperature is greater than 1 
   degree higher td seconds before during defrost and open door conditions

Front Panel Operation

Set Point Setup

• Press the Set key once and SEt will be displayed.
• Press Set key again and set point value will be shown.
• Uses the Up and Down arrows to adjust set point.
• Press the Set key to save the new set point.
• Press Set and Down arrow at same time to exit.

Time Setup

• Press the Set Key once and SEt will be displayed.
• Use the Up and Down arrow until Hor is displayed for adjusting the hours.
• Press the Set key to view the current value.
• Use the Up and Down arrow to adjust to current time.
• Press the Set key for 8 seconds to save the new time (PrO will flash on display

once the value is saved).

• Press the Set key to return to the previous menu.
• Use the Up and Down arrow until nin is displayed for adjusting the minutes.
• Repeat steps 3 through 6.
• Press the Set and Down arrow at the same time to exit.