Lovato DME D300 T2 MID Instruction Manual Download Page 5

I306 GB I 06 19

                                               31100141

5

PARAMETERS SETTING (SETUP)
–   While display is showing 

SETUP

, press  . 

–   The display shows the first parameter code 

P1-01

.

–   To move to next parameters 

P2-01, P2-02

… etc, use 

.

–   When the display indicates the code of the parameter that needs to be modified, press  . 

•  The display shows its present value of the parameter. Pushing 

the value can be modified. 

   By clicking 

at the same time, the default value is set.

•  Confirm with 

to go back to parameter code selection.

–   Pressing buttons 

together for 1s, parameters are saved and system goes back to normal

operation. 

L M

L M

L M

L M

IMPOSTAZIONE PARAMETRI (SETUP)
–   Con il display che indica 

SETUP

, premere  . 

–   Il display indica il codice del primo parametro 

P1-01

–   Per selezionare i parametri successivi 

P2-01, P2-02

… usare 

.

–   Quando il display indica il codice del parametro che si desidera modificare, premere 

.

•  Il display indica il valore attuale dell’impostazione del parametro. Il valore del parametro può 

   essere modificato con 

.

   Premendo contemporaneamente 

viene proposto il valore di default.

•  Confermando con 

si può tornare alla selezione parametri. 

–   Mentre il display visualizza il codice di una parametro, premendo 

per 1s, i parametri

vengono salvati e si torna al funzionamento normale.

L M

L M

L M

L M

 Code                  Description                                        Default                                Range
 
 

 P1-01                Password                                            0000                             0000 - 9999

 P1-02                Exported energies viewing                   OFF                                  OFF-ON

                           enable

 P2-01                Output 1 function                                 OFF                            OFF - Disabled

                                                                                                                        1000 PUL / kWh 
                                                                                                                         100 PUL / kWh
                                                                                                                          10 PUL / kWh 
                                                                                                                           1 PUL / kWh
                                                                                                                                THR –

                                                                                                                Programmable thresholds

 P2-02                Reference measure for                         01                               (see table 1)

                           threshold 1                                           kW                                        

 P2-03                ON Threshold 1                                  10.00                       -9999.99 – 9999.99

 P2-04                ON delay 1                                         5 sec.                           0 – 9999 sec.

 P2-05                OFF Threshold 1                                  5.00                        -9999.99 – 9999.99

 P2-06                OFF delay 1                                        5 sec.                           0 – 9999 sec.

 P3-01                Output 2 function                                 OFF                            OFF - Disabled

                                                                                                                        1000 PUL / kWh 
                                                                                                                         100 PUL / kWh
                                                                                                                          10 PUL / kWh 
                                                                                                                           1 PUL / kWh
                                                                                                                                THR –

                                                                                                                Programmable thresholds

 P3-02                Reference measure for                         01                               (see table 1)

                            threshold 2                                          kW                                        

 P3-03                ON Threshold 2                                  10.00                       -9999.99 – 9999.99

 P3-04                ON delay 2                                         5 sec.                           0 – 9999 sec.

 P3-05                OFF Threshold 2                                  5.00                        -9999.99 – 9999.99

 P3-06                OFF delay 2                                        5 sec.                           0 – 9999 sec.

 P4-02                Reference measure for                         01                               (see table 1)

                           threshold 3                                           kW                                        

 P4-03                ON Threshold 3                                  10.00                       -9999.99 – 9999.99

 P4-04                ON delay 3                                         5 sec.                           0 – 9999 sec.

 P4-05                OFF Threshold 3                                  5.00                        -9999.99 – 9999.99

 P4-06                OFF delay 3                                        5 sec.                           0 – 9999 sec.

 P5-01                Function for Input 1                             OFF                            OFF – Disabled
                                                                                                                          ON - Enabled

                                                                                                                    TAR – Tariff selection 
                                                                                                             CLEAr P – Clear partial energy
                                                                                                               CLEAr H – Clear hour meter
                                                                                                              CLEAr d - Clear max demand

 P6-01                Hour counter 1 enable                         OFF                          OFF-ON-THR-INP

 P6-02                Hour counter 2 enable                         OFF                          OFF-ON-THR-INP

 P6-03                Hour counter 3 enable                         OFF                          OFF-ON-THR-INP

 P7-01                Enable demand                                    OFF                                  OFF-ON

                           measurements

 P7-02                Reactive power                                   FUND                              TOT-FUND

                           calculation method

TABELLA PARAMETRI DI SETUP

SETUP PARAMETER TABLE

 Codice               Descrizione                                       Default                                Range
 
 

 P1-01                Password                                            0000                             0000 - 9999

 P1-02                Visualizzazione energie                        OFF                                  OFF-ON

                           esportate

 P2-01                Scelta funzione uscita 1                       OFF                          OFF - Disabilitata

                                                                                                                        1000 PUL / kWh 
                                                                                                                         100 PUL / kWh
                                                                                                                          10 PUL / kWh 
                                                                                                                           1 PUL / kWh
                                                                                                                                THR –
                                                                                                                    Soglie programmabili

 P2-02                Misura di riferimento                            01                           (vedere tabella 1)

                           per soglia 1                                          kW                                        

 P2-03                Soglia ON 1                                        10.00                       -9999.99 – 9999.99

 P2-04                Ritardo soglia ON 1                            5 sec.                           0 – 9999 sec.

 P2-05                Soglia OFF 1                                        5.00                        -9999.99 – 9999.99

 P2-06                Ritardo soglia OFF 1                           5 sec.                           0 – 9999 sec.

 P3-01                Scelta funzione uscita 2                       OFF                          OFF - Disabilitata

                                                                                                                        1000 PUL / kWh 
                                                                                                                         100 PUL / kWh
                                                                                                                          10 PUL / kWh 
                                                                                                                           1 PUL / kWh
                                                                                                                                THR –
                                                                                                                    Soglie programmabili

 P3-02                Misura di riferimento                            01                           (vedere tabella 1)

                           per soglia 2                                          kW                                        

 P3-03                Soglia ON 2                                        10.00                       -9999.99 – 9999.99

 P3-04                Ritardo soglia ON 2                            5 sec.                           0 – 9999 sec.

 P3-05                Soglia OFF 2                                        5.00                        -9999.99 – 9999.99

 P3-06                Ritardo soglia OFF 2                           5 sec.                           0 – 9999 sec.

 P4-02                Misura di riferimento                            01                           (vedere tabella 1)

                           per soglia 3                                          kW                                        

 P4-03                Soglia ON 3                                        10.00                       -9999.99 – 9999.99

 P4-04                Ritardo soglia ON 3                            5 sec.                           0 – 9999 sec.

 P4-05                Soglia OFF 3                                        5.00                        -9999.99 – 9999.99

 P4-06                Ritardo soglia OFF 3                           5 sec.                           0 – 9999 sec.

 P5-01                Scelta funzione ingresso 1                   OFF                          OFF - Disabilitato 

                                                                                                                          ON - Abilitato

                                                                                                                   TAR - Selezione tariffa 

                                                                                                                  CLEAr P - reset parziali

                                                                                                                 CLEAr H - reset contaore
                                                                                                              CLEAr d - reset max demand

 P6-01                Abilitazione contaore 1                        OFF                          OFF-ON-THR-INP

 P6-02                Abilitazione contaore 2                        OFF                          OFF-ON-THR-INP

 P6-03                Abilitazione contaore 3                        OFF                          OFF-ON-THR-INP

 P7-01                Abilitazione misure                              OFF                                  OFF-ON

                           demand

 P7-02                Calcolo potenza reattiva                     FUND                              TOT-FUND

PARAMETER DESCRIPTION

P1-01

– If set to 0000 (default) the password protection is disabled.

Any other setting defines the password to access to the advanced functions. 

P1-02

– Enabling of exported energies viewing.

P2-01

– Defines the function of the static output 1 from the following list:

OFF

- Disabled.

1000 PUL …1 PUL

– Static output 1 operates as a pulse emitter for active energy count. These

selections define the number of pulses sent for every kWh.

THR

– The static output 1 becomes an alarm threshold for maximum or minimum limit, depending

on values programmed in P2-03 and P2-05. The threshold is used by hour counter 1 as well, if
enabled.
If P2-03 >= P2-05, then output activates when the measure defined by P2-02 is higher than P2-03,
and de-activates when its value becomes less than P2-05 (maximum limit with hysteresis). 
If P2-03 < P2-05, then output activates when the measure defined by P2-02 is lower than P2-03, and
activates when its value becomes higher than P2-05 (minimum limit with hysteresis). 

P2-02

– Selection of measure to compare with thresholds. See table 1.

DESCRIZIONE PARAMETRI

P01-01 

– Se impostato a 0000 (default) la protezione da password è disabilitata. Qualsiasi altra

impostazione definisce la password di accesso alle funzioni avanzate.

P1-02

– Abilita la visualizzazione delle energie esportate.

P02-01

– Definisce la funzione dell’uscita statica programmabile 1:

OFF

- Disabilitata.

1000 PUL …1 PUL

– L’uscita statica 1 funziona come emettitore di impulsi per il conteggio

dell’energia attiva. Con queste selezioni si definisce il numero di impulsi per per ogni kWh.

THR

– programma l’uscita 1 come soglia di allarme di massima oppure di minima, a seconda dei

valori impostati in P2-03 e P2-05. La soglia è utilizzata anche dal contaore 1, se abilitato.
Se P2-03 >= P2-05, allora l’uscita si attiva quando la misura specificata da P2-02 diventa > P2-03, e
si disattiva quando ritorna ad essere < P2-05 (funzione di soglia massima con isteresi).
Se invece P2-03 < P2-05, allora l’uscita si attiva quando la misura specificata da P2-02 diviene < P2-
03, e si disattiva quando ritorna ad essere > P2-05 (funzione di soglia minima con isteresi). 

P2-02

– Selezione misura alla quale vengono applicate le soglie. Vedere la tabella 1.

Summary of Contents for DME D300 T2 MID

Page 1: ...des Gebäudes ist ein Ausschalter oder Trennschalter einzubauen Dieser muss sich in unmittelbarer Nähe des Geräts befinden und vom Bediener leicht zugänglich sein Er muss als Trennvorrichtung für das Gerät gekennzeichnet sein IEC EN 61010 1 6 11 3 1 Das Gerät mit einem weichen Tuch reinigen keine Scheuermittel Flüssigreiniger oder Lösungsmittel verwenden ADVERTENCIA Leer atentamente el manual antes...

Page 2: ... power 2 programmable static outputs AC input for two tariff selection INDICE Pagina Introduzione 2 Descrizione 2 Selezione misure 3 LED metrologico frontale 4 Indicazione flusso energia 4 Uscite statiche programmabili 4 Ingresso in AC programmabile 4 Funzioni avanzate 4 Password dimenticata o persa 4 Impostazione parametri setup 5 Tabella dei parametri di setup 5 Sigilli metrologici e marcature 7...

Page 3: ... Σ L1 L2 L3 kvarh T2 Exported reactive energy Tariff 2 000000 0 Σ L1 L2 L3 V Voltage phase neutral and 000 0 Σ L1 L2 L3 phase phase Σ L1L2 L2L3 L3L1 A Current 00 00 L1 L2 L3 kW Active power 00 00 Σ L1 L2 L3 kvar Reactive power 00 00 Σ L1 L2 L3 kVA Apparent power 00 00 Σ L1 L2 L3 PF Power factor cos 0 00 Σ L1 L2 L3 Hz Frequency 00 0 h Part Hour counter hhhhh mm 00000 00 L1 L2 L3 kW d Average active...

Page 4: ...ata o prodotta ovvero 1 impulso per ogni Wh Se da almeno una delle tre fasi viene esportata energia il LED indica l energia totale come bilancio tra l energia importata e esportata La frequenza di lampeggio del LED dà una immediata indicazione dell entità della potenza in un determinato istante La durata del lampeggio il colore e l intensità del LED sono conformi alle norme che prescrivono il suo ...

Page 5: ... 05 Soglia OFF 1 5 00 9999 99 9999 99 P2 06 Ritardo soglia OFF 1 5 sec 0 9999 sec P3 01 Scelta funzione uscita 2 OFF OFF Disabilitata 1000 PUL kWh 100 PUL kWh 10 PUL kWh 1 PUL kWh THR Soglie programmabili P3 02 Misura di riferimento 01 vedere tabella 1 per soglia 2 kW P3 03 Soglia ON 2 10 00 9999 99 9999 99 P3 04 Ritardo soglia ON 2 5 sec 0 9999 sec P3 05 Soglia OFF 2 5 00 9999 99 9999 99 P3 06 Ri...

Page 6: ...impostato su ON P6 03 Definisce il funzionamento del contaore 3 OFF Contaore disabilitato non viene visualizzato ON Il contaore si incrementa fintanto che l energy meter è alimentato THR Il contaore si incrementa fintanto che la soglia definita con i parametri P4 xx è attivata INP Il contaore si incrementa fintanto che l ingresso programmabile è attivato Il parametro P5 01 deve essere impostato su...

Page 7: ...sibile una etichetta posizionata all interno dello strumento con riportato il numero di serie del contatore 4 sigilli laterali etichette antimanomissione impediscono l apertura del contenitore e l accesso ai circuiti interni I coprimorsetti piombabili quando installati con gli opportuni sigilli impediscono l accesso ai morsetti e cablaggi I sigilli sull apparecchio devono presentarsi intatti come ...

Page 8: ... the meter must be mounted in a class IP51 enclosure or better IEC EN 60529 TECHNICAL CHARACTERISTICS Voltage Nominal voltage Us 400V 3N Operating voltage range 323 456V 3N Rated frequency 50Hz Operating frequency range 45 66Hz Power consumption dissipation 2 5VA 1W Current Minimum current Imin 0 75A Transition current Itr 1 5A Reference current Iref Ib 15A Max current Imax 80A Start current Ist 6...

Page 9: ...ado di protezione minimo IP51 IEC EN 60529 CARATTERISTICHE TECNICHE Tensione Tensione nominale Us 400V 3N Limiti di funzionamento 323 456V 3N Frequenza nominale 50Hz Limiti di funzionamento 45 66Hz Potenza assorbita dissipata 2 5VA 1W Corrente Corrente minima Imin 0 75A Corrente di transizione Itr 1 5A Corrente di riferimento Iref Ib 15A Corrente massima Imax 80A Corrente di start Ist 60mA Accurat...

Reviews: