background image

I586 GB 01 19

12

Manual mode (MAN)
In MAN mode the PID control is de-activated and the variable speed drive works with manual regulation of the frequency setpoint via a potentiometer connected to the AI2 analog input (type 0-10V).

In this example we configure the variable speed drive to provide an output frequency of 0Hz when the potentiometer is at minimum of its regulation scale (0V) and a frequency of 50Hz when the potentiometer is at
maximum (10V).

Example of use.
Once the parameters listed above have been set on the VLA1, test the functioning:
–   Keep opened the DI2 digital input to allow the enable of the automatic mode (AUT).

–   With the 

buttons of the keypad set a PID setpoint, which for this specific example it corresponds to a pressure setpoint. For example, set a PID setpoint of 4.0 PID Unit (= 4 Bar).

–   The VLA1 read the value of the pressure of the plant (PID feedback) from the AI1 analog input, to which is connected the output of a pressure sensor. The 0- 10V voltage signal of the pressure sensor is

automatically transformed by the VLA1 in a pressure value according to the parameters previously set (in this example: 0V = 0 Bar, 10V = 15 Bar).

–   Close the DI1 digital input to run the motor.
–   If the pressure of the plant is lower than the setpoint (e.g. 2 Bar, which is lower than 4 Bar) the VLA1 increases the speed of the motor by regulating the output frequency until the PID setpoint is reached. In this

specific example, the output frequency of the drive when PID control is active is limited to the 20% and 80% of the maximum frequency (50Hz), which means from 10Hz to 40Hz.

–   If you want to switch the operating mode to manual mode (MAN) close the DI2 digital input.
–   Now the PID control is de-activated (the value of AI1 signal is ignored). The output frequency of the drive is adjusted with the external potentiometer, connected to the AI2 analog input. In this specific example, the

output frequency regulated with the potentiometer can be adjusted from 0Hz to 50Hz.

–   To command the motor stop, open the DI1 digital input.

         Parameter              Function                                                                                                                                  Setting                Description

          P201.01               Frequency setpoint source                                                                                                           3                     Frequency adjusted with analog input 2 (AI2)

          P201.02               PID setpoint source                                                                                                                     1                     PID setpoint adjusted from keypad

          P210.00               Minimum frequency                                                                                                                  0 Hz                  Insert the value of the minimum frequency

          P211.00               Maximum frequency                                                                                                                50 Hz                 Insert the value of the maximum frequency

          P220.00               Acceleration time                                                                                                                      5 sec                 Insert the value of the acceleration time

          P221.00               Deceleration time                                                                                                                      5 sec                 Insert the value of the deceleration time

  I/O configuration (AI1 = PID feedback, AI2 = frequency setpoint, DI1 = run/stop, DI2 = AUT-MAN mode switch)

          P430.01               Analog input 1 (AI1) configuration                                                                                              0                     Analog signal type 0-10V

          P430.04               PID value when AI1 is at minimum                                                                                             0                     Minimum value of AI1 signal expressed in PID Unit (0V = 0 PID unit, in this 

                                                                                                                                                                                                                  example correspondent to 0 Bar of pressure)

          P430.05               PID value when AI1 is at maximum                                                                                            15                    Maximum value of AI1 signal expressed in PID Unit (10V = 15 PID unit, in this

                                                                                                                                                                                                                  example correspondent to 15 Bar of pressure)

          P431.01               Analog input 2 (AI2) configuration                                                                                              0                     Analog signal type 0-10V

          P431.02               Frequency value when AI2 is at minimum                                                                                0 Hz                  Insert the frequency value correspondent to AI2 signal at minimum (0V)

          P431.03               Frequency value when AI2 is at maximum                                                                               50 Hz                 Insert the frequency value correspondent to AI2 signal at maximum (10V)

          P400.02               Run/stop command                                                                                                                    11                    Run/stop command from digital input DI1

          P400.45               Deactivate PID control                                                                                                                12                    DI2 opened = PID enabled, provided that P600.01=1 (AUT mode)

                                                                                                                                                                                                                  DI2 closed = PID disabled (MAN mode)

   Configuration of PID parameters (AUT mode)

          P600.01               PID enable                                                                                                                                   1                     PID function enabled

          P600.02               PID feedback source                                                                                                                    1                     PID feedback connected to analog input AI1

          P600.05               Minimum PID operating frequency                                                                                           20%                  Minimum value of the operating frequency of the PID control expressed as % 

                                                                                                                                                                                                                  of the maximum frequency of the drive P211.00 (100% = P211.00 = 50Hz)
                                                                                                                                                                                                                  In this example: 20% of 50Hz = 10Hz

          P600.06               Maximum PID operating frequency                                                                                           80%                  Maximum value of the operating frequency of the PID control expressed as % 

                                                                                                                                                                                                                  of the maximum frequency of the drive P211.00 (100% = P211.00 = 50Hz)
                                                                                                                                                                                                                  In this example: 80% of 50Hz = 40Hz

          P605.01               Minimum value of the PID setpoint                                                                                             2                     Minimum value of the settable PID setpoint, expressed in PID unit.

                                                                                                                                                                                                                  In this example: 2 PID Unit, correspondent to 2 Bar of pressure.

          P605.02               Maximum value of the PID setpoint                                                                                             8                     Maximum value of the settable PID setpoint, expressed in PID unit.

                                                                                                                                                                                                                  In this example: 8 PID Unit, correspondent to 8 Bar of pressure.

          P606.01               PID acceleration time                                                                                                               10 sec                Insert the acceleration time of the PID control

          P606.02               PID deceleration time                                                                                                              10 sec                Insert the deceleration time of the PID control

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for VLA1 series

Page 1: ...etpoint adjusted with keypad and feedback signal type 0 10V 7 4 8 PID Control Setpoint adjusted with keypad and feedback signal type 4 20mA 7 5 Motor parameters 8 6 Additional functions 9 6 1 Configur...

Page 2: ...full keypad control Reversal of rotation direction Example of navigation in the menu of the VSD and modification of a parameter Back to the previous level Back to the previous level Back to the previo...

Page 3: ...ings follow this procedure Set the parameter P700 01 1 load default settings Press the button several times to exit from the programming menu until it appears the text STOP Keep pressed the button for...

Page 4: ...P400 02 Run stop command 11 Run stop command from digital input DI1 connected between terminals DI1 24V NO COM NC GND AI1 AI2 AO1 10V 24V DI1 DI2 DI3 DI4 DI5 DO1 GND Parameter Function Setting Descri...

Page 5: ...deceleration time P430 01 Analog input 1 AI1 configuration 0 Analog signal type 0 10V P430 02 Value of frequency when AI1 is at minimum 0Hz Frequency when AI1 is at minimum AI1 0V P430 03 Value of fr...

Page 6: ...11 00 Maximum frequency 50Hz Insert the value of the maximum frequency P220 00 Acceleration time 5sec Insert the value of the acceleration time P221 00 Deceleration time 5sec Insert the value of the d...

Page 7: ...mum frequency P220 00 Acceleration time 5sec Insert the value of the acceleration time P221 00 Deceleration time 5sec Insert the value of the deceleration time P430 01 Analog input 1 AI1 configuration...

Page 8: ...If you need to enable the sensorless vector control set P300 00 4 All the other parameters must be left to default settings Parameter Function Setting Description P327 04 Automatic motor data identifi...

Page 9: ...greater than the threshold set in P412 00 78 Function current limit reached the relay switches when the motor current is greater or equal to the maximum threshold set in P324 00 calculated as of the m...

Page 10: ...ange 0 10VDC correspondent to the output frequency range 0 50Hz Parameter Function Setting Description P440 01 AO1 analog output range 1 0 10VDC P440 02 AO1 analog output function 1 Actual output freq...

Page 11: ...sensor with output 0 10V correspondent to a pressure of 0 15Bar with a linear characteristic as shown in the following diagram This means that if the output of the sensor is 0V it means a pressure of...

Page 12: ...210 00 Minimum frequency 0 Hz Insert the value of the minimum frequency P211 00 Maximum frequency 50 Hz Insert the value of the maximum frequency P220 00 Acceleration time 5 sec Insert the value of th...

Page 13: ...mic performance of the load profile overvoltage display in parameter P208 06 results from the Check mains voltage setting of the rated mains voltage in P208 01 Check settings for the brake energy mana...

Reviews: