LOVATO ELECTRIC LAWN DME D121 Instruction Manual Download Page 3

 

                       Doc: MHIT300B0408.docx                                22/11/2013                                         p. 3 / 7 

Indicazione di collegamento errato 

x

In caso di collegamento errato, quando l’apparecchio rileva un flusso di 

energia di direzione contraria, viene attivata l’indicazione lampeggiante 

Err3

x

Questo errore può essere provocato dalla inversione del collegamento della 

corrente (morsetti L



e L

‚

) oppure dalla inversione dei morsetti della 

tensione (N - L



). 

x

In queste condizioni l’energia non viene conteggiata. 

 

 

 
 

Incorrect wiring indication 

x

In case of incorrect wiring, when the device detects a reverse energy 

flow, the display shows the blinking code  

Err 3

x

This error is caused by either reverse connection of current  wires 

(terminals  L



and L

‚

) or  reverse voltage wiring (terminals N - L



). 

x

In these conditions the energy is not counted. 

 

Navigazione tramite tasto frontale 

x

Per muoversi fra i menu si usano le seguenti regole: 

x

Una breve pressione del tasto frontale, che indicheremo con 

 

,

 viene 

utilizzata per cambiare la selezione attualmente visualizzata con una 
diversa, successiva.  

x

Una pressione prolungata (> 3s), che indicheremo con 

 , viene invece 

utilizzata per confermare la selezione visualizzata. 

x

Il simbolo   indica quando è necessario attendere perché il display 

proponga una nuova scelta. 

x

Per uscire da un menu, selezionare 

--ESC--

 . 

 

Funzioni avanzate 

x

Per accedere alle funzioni avanzate utilizzare la seguente procedura: 

1.

Partendo da una qualsiasi visualizzazione, premere 

. Se la 

protezione da password è disattivata (default di fabbrica, password = 
0000) il display salta direttamente al punto 4, altrimenti indica 

PASS

 per 

evidenziare la necessità di inserire la password. 

2.

Rilasciare il tasto. Il display ora attende l’inserimento della password e 
indica 

0000

. Le singole cifre lampeggiano a rotazione. Premendo 

 

mentre una cifra sta lampeggiando, essa viene incrementata. Attendendo 
qualche secondo, la cifra successiva inizia a lampeggiare. Dopo avere 
inserito la password premere il tasto 

 per confermare. 

3.

Se la password inserita non è corretta il display mostra 

PASS E

r

 e torna 

alla visualizzazione normale. Se invece è corretta, si passa al punto 
successivo. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

4.

Il display indica la prima delle scelte nella seguente lista. Per passare da 
una scelta alla successiva premere 

 

 

x

CLEAR P 

 = azzeramento contatori di energia parziali 

x

CLEAR h

  = azzeramento contaore parziale (se abilitato)  

x

CLEAR d

  = azzeramento max demand (se abilitato) 

x

SETUP

 = programmazione parametri 

x

INFO

   = revisione software e checksum interno  

x

--ESC--

  = ritorno al funzionamento normale 

 

5.

Per selezionare una funzione premere  

 mentre viene visualizzata la 

funzione desiderata.  

6.

Se non vengono premuti tasti per 60 secondi l’apparecchio ritorna 
automaticamente al funzionamento normale. 

 

 

Navigation with front key 

x

To move through menus use the following rules:  

x

A short click of the front button, indicated by 

,

 changes the present 

selection, shown on the display, with a new one (the following).  

x

Pressing the button for a long time (> 3s), that we will indicate with 

symbol 

 

,

 is used to confirm the present selection. 

x

Symbol   indicates when the user must wait for the display to move to 

a new selection. 

x

To quit a menu, select the 

--ESC--

 option.  

 
 

Advanced functions 

x

To access the advanced functions, use the following procedure:  

1.

Starting from any visualization screen, press 

. If the password 

protection is disabled (factory default, password = 0000), display 
jumps directly to point 4, otherwise it will show 

PASS

  to inform that the 

access code must be entered first. 

2.

Release the button. The display now waits for the password and 
indicates 

0000

. The single digits are flashing sequentially. Pressing  

 while a digit is flashing, that digit is incremented. Waiting for 

some seconds, the selection moves to the next digit. After having 
entered the right password code, press 

  to confirm. 

3.

If the entered password is wrong, the display shows 

PASS

 

E

r

 and goes 

back to normal visualization. If instead the code is correct, it proceeds   
to next point.  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

4.

The display shows the first item of the following list. To move through 
the list, click 

  

 

x

CLEAR P  

= clearing of partial energy meters  

x

CLEAR h  

= clearing of partial hour counter (if enabled)

  

x

CLEAR d  

= clearing of max demand values (if enabled) 

x

SETUP 

= parameters programming (setup) 

x

INFO 

= revision and checksum of internal software  

x

--ESC--  

= returns to normal operation 

 

5.

To select a function, press  

 while the desired function is 

displayed.  

6.

If the button is never pressed for 60 consecutive seconds, the display 
goes back automatically to normal operation. 

Summary of Contents for LAWN DME D121

Page 1: ...correct wiring indication 3 Navigation with front key 3 Advanced functions 3 Parameter setting setup 4 Setup parameter table 5 Modbus addresses table 5 Mechanical dimensions mm 6 Wiring diagrams 6 Tec...

Page 2: ...D colour and intensity are compliant with the reference standards that define its utilization in order to verify the accuracy of the energy meter Indicazione flusso di energia x Quando lo strumento st...

Page 3: ...nella seguente lista Per passare da una scelta alla successiva premere x CLEAR P azzeramento contatori di energia parziali x CLEAR h azzeramento contaore parziale se abilitato x CLEAR d azzeramento ma...

Page 4: ...le cifre lampeggiano a rotazione Premendo mentre una cifra sta lampeggiando essa viene incrementata Attendendo comincia a lampeggiare la cifra successiva o Se invece il parametro prevede la scelta fra...

Page 5: ...ritardo per attivazione uscita Nota le misure vengono aggiornate ed integrate 1 volta al secondo quindi questo ritardo ha una variabilit da 0 a 1 secondo P 06 e P 07 Come sopra per disattivazione usci...

Page 6: ...e device the measures listed in the following table Address Measure Word UoM 1A20h Total active energy 2 Wh 1A2Ah Partial active energy 2 Wh 1A24h Total reactive energy 2 Varh 1A2Eh Partial reactive e...

Page 7: ...urti 10g IEC EN 60068 2 27 Shock resistance 10g IEC EN 60068 2 27 Resistenza alle vibrazioni 0 7g IEC EN 60068 2 6 Vibration resistance 0 7g IEC EN 60068 2 6 Ambiente meccanico Classe M1 Mechanical en...

Reviews: