Installation
(For Qualified Installers Only)
13
© Travis Industries
4141007
100-01402
Mobile Home Requirements
Outside air is required (used for combustion) - see the directions below.
The heater must be bolted to the floor (Some states do not require this; check with your local building
department).
The heater must be grounded to the steel chassis of the mobile home (Some states do not require this;
check with your local building department).
DO NOT INSTALL IN SLEEPING ROOM.
CAUTION:
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
Outside Air (Used for Combustion
Part #99200139)
Must not be drawn from an enclosed space (garage, unventilated crawl space).
HINT:
Travis Industries strongly recommends outside air for all residential installations,
especially for those that are energy efficient, air-tight homes, or when using vent without rise.
Must not be over 48” (1220mm) long
Must be made with 3” (76mm) diameter or larger metal or aluminum duct with a metal screen
attached to the end to keep out rodents (P.V.C. or other combustible materials may not be used).
We recommend the Travis Industries Outside Air Kit (part # 99200139).
Must not terminate above or within 1' (305mm) of the chimney termination.
Must have a rain cap or down-turned elbow to prevent water from entering.
Must be located so that it will not become plugged by snow or other material.
3" Air Duct
A screen is required to prevent
rodents from entering.
Outside air entrance must be placed so it
does not become blocked by snow.
Air may be drawn from a ventilated crawl space.