LRF-3300S Ultrasonic Transit-time Flow meter
- 50 -
For example, to read address 1 (0x01) of the flowmeter 40002 register data in the RTU mode, the flowmeter
considers it to be invalid data, and sends the following command:
0x01
0x03
0x00 0x01
0x00 0x01
0xD5 0xCA
Flow meter Address Function Code Register Address Register Number CRC Verify Code
Flow meter returned error code is:
0x01
0x83
0x02
0xC0 0xF1
Flow meter Address Error Code Error Extended Code CRC Verify Code
5.
MODBUS Register Address List
The flow meter MODBUS Register has a read register and a write single register.
a)
Read Register Address List (use 0x03 function code to read)
PDU
Address
Register
Read
Write
Type
No. registers*
$0000
40001
Flow/s - low word
32 bits real
2
$0001
40002
Flow/s - high word
$0002
40003
Flow/m - low word
32 bits real
2
$0003
40004
Flow/m- high word
$0004
40005
Flow/h - low word
32 bits real
2
$0005
40006
Flow/h - high word
$0006
40007
Velocity – low word
32 bits real
2
$0007
40008
Velocity – high word
$0008
40009
Positive total – low word
32 bits int.
2
$0009
40010
Positive total – high word
$000A
40011
Positive total – exponent
16 bits int.
1
$000B
40012
Negative total – low word
32 bits int.
2
$000C
40013
Negative total – high word
$000D
40014
Negative total – exponent
16 bits int.
1
$000E
40015
Net total – low word
32 bits int.
2