3
Power consumption
One power supply has an output of 1 A (1000 mA). Use
this list to calculate if you need a power barrier.
Product
mA (Peak)
CO2 Mk9 Detector SET 4 A
177
CO2 Mk90 Stand-Alone Base SET
200
CO2 Sensor Mk9
75
Central Unit Mk9
35
CO2 Sensor Mk90
120
O2 Sensor Mk9
42
Sniffer
16
Power Barrier
17
Horn/Strobe LED Amber
80
Remote Connection Box (relay)
20
Remote Connection Box (reset
button)
45
Safe Mode Box and Shut off Valve
196