Analog Inputs
The analog inputs are voltage inputs specified with an operating range of 0V to 10V DC. The
conversion resolution is up to 12 bit (0..4095). Please consult the RTCU IDE documentation for
further details.
The input signal is connected between AINx and AGND. AGND must be connected to the
reference of the connected equipment. Please be aware that deviations may occur, as the system is
very noise sensitive. Avoid long unshielded wires, and large fast-changing signals routed parallel
to the analog signals.
The inputs are low-pass filtered, ESD- and transient protected.
X3: 16 pin I/O connector overview.
Pin
Name
Description
7
AIN 1
Analog input 1
8
AIN 2
Analog input 2
15
AGND
Analog Ground
16
AGND
Analog Ground
Specification for each analog input:
Min.
Typ.
Max.
Unit
0
-
10
VDC
Protected against transients and
low-pass filtered
Precision is based on
measurements @ 25 ˚C
Resolution
-
-
12
Bit
Precision
-
0.15
0.3
%FSR
Cut-off frequency
-
4.5
-
kHz
Input impedance
-
40
-
kΩ