Alarm number
Type
Name
Description
Elimination
Hardware
200
Critical
LOM9
missing
LOM9 missing
Check connection
Operation
600
Warning
Hi Pres
High pressure switch active
The unit restarts when the pressure drops below
high pressure switch low-limit again.
Check hot side pump/overflow valve on high
temperature side.
After 3
rd
cutout the alarm must be acknowledged
to start the unit again.
601
Critical
Low pres.
Low pressure switch active
Check refrigerant charge and expansion valve.
The alarm must be acknowledged to start the unit
again.
602
Critical
Leakage
Low pressure in brine - brine
pressure switch active
Leakage check of the brine system.
The alarm must be acknowledged to start the unit
again.
603
Critical
Hi pres
High pressure switch
repeatedly active
Check hot side pump/overflow valve on high
temperature side.
The alarm must be acknowledged to start the unit
again.
604
Warning
Frost pro-
tection
Temperature too low
(state freeze protect)
Heat pump and electrical heater running full
capacity.
Check that setting are not turned off.
605
Warning
Heat pump
overheat
Supply temperature too high
(condition total stop)
Check hot side pump/overflow valve on high
temperature side.
606
Warning
Solar panel
overheat
Solar panel is in forced stop
condition.
(SP state Forced stop)
Check connection to external temperature
adjustment.
607
Warning
Legionella
failed
Anti Legionella function has
timed out twice.
Check electrical heaters and supply of heat to
brine circuit.
Internal controller error
904
Warning
Datalog
Error with internal log
Reserved. Not implemented yet.
905
Warning
Database
Error with internal database
Controller may be defect. Try update the firmware
or replace the controller.
907
Warning
RTC err
Error with the internal real
time clock
Replace the controller.
908
Warning
RTC inv
Invalid data from the real
time clock
Unit powered off to long. Set time and date. Else
replace the controller.
998
Warning
TestVer.
The software is a test version
Use the release version of the software.
999
Warning
Manual
mode
The unit is in manual mode
Change mode from Manual to On.
Alarms system