PUMP-Rec-05
PUMP
Recommendation
PUMP RECOMMENDATION FOR
COPPER-FIN 0986-2066 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
ARM3024PAB 1/2 2-1/2" Brass
Brass Armstrong
2B1050 Horizontal
Installation Specifications
Recommended for
Based on
Pump
Model Numbers
Maximum GPM
Installation Type
Copper-Fin Wtr Htr, CW(N,L) 0986-2066
90 GPM
Single Water Heater piped to Single Storage Tank
ARM3024PAB
Based on
Based on
Minimum Pipe Diameter
Connecting piping
2-1/2"
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee
IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-REC-All Pumps” for alternate pumps and pump curves.
OIL PORT
A
C
16”
19-1/2”
B
D
11-1/2”
2