background image

 

 
 
 

 

PUMP RECOMMENDATION FOR 

POWER-FIN 0502-1302 WATER HEATER 

 

Pump Specifications 

Part No. 

HorsePower 

Flanges 

Valute Material 

Flange Material 

Vendor 

Vendor Product Series 

Orientation 

PUM3013 2/5  2"  Brass 

Brass  Armstrong E 

Series 

Horizontal 

 
Installation Specifications 

  

Recommended for 

Based on 

      Pump 

Model Numbers 

Maximum GPM 

Installation Type 

  

Power-fin, PF(N,L) 0502-1302 

75 GPM 

Single Water Heater piped to Single Storage Tank 

PUM3013 

Based on 

Based on 

  

  

Minimum Pipe Diameter 

Connecting piping 

  

  

2-1/2" 

Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee  

 
IMPORTANT: Read the Power-fin 0502-2001 Installation and Operation Manual.  If the planned system exceeds 
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.

 

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

PUMP 

Recommendation 

PUMP-Rec-16 Rev C 

Reviews: