1
PUMP RECOMMENDATION FOR
POWER-FIN 0502-1302 WATER HEATER
Pump Specifications
Part No.
HorsePower
Flanges
Valute Material
Flange Material
Vendor
Vendor Product Series
Orientation
PUM3013 2/5 2" Brass
Brass Armstrong E
Series
Horizontal
Installation Specifications
Recommended for
Based on
Pump
Model Numbers
Maximum GPM
Installation Type
Power-fin, PF(N,L) 0502-1302
75 GPM
Single Water Heater piped to Single Storage Tank
PUM3013
Based on
Based on
Minimum Pipe Diameter
Connecting piping
2-1/2"
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee
IMPORTANT: Read the Power-fin 0502-2001 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.
PUMP
Recommendation
PUMP-Rec-16 Rev C