background image

 26 • Residen  al Standard Gas Water Heater Use and Care Guide

TR

OUBLE

SHOO

TING

 26 • Residen  al Standard Gas Water Heater Use and Care Guide

TROUBLESHOOTING

plumbing system can make it appear 
that the water heater is producing 
li  le to no hot water. In this case, the 
burner will be on all or almost all the 

 me, yet you will have very li  le hot 

water. Locate and repair the leak. 

Sediment or Lime in Tank. 

With an ex-

is  ng water heater, if you have some 
hot water but not as much as you’re 
used to, there may be a build up of 
sediment or lime on the bo  om of the 
tank. Sediment or lime build up can 
reduce the effi

  ciency of your water 

heater. Heavy deposits can damage 
the water heater. See the Mainte-
nance sec  on for steps on draining 
and fl ushing the water heater.

Temperature Too High

Adjust the thermostat on the water 
heater to a lower se   ng. Install or 
adjust Thermosta  c Mixing Valves 
for each point-of-use (see the valve 
manufacturer’s instruc  ons). 

Low Water Pressure

Check both the cold and hot water 
at a sink to determine if the lower 
pressure is only on the hot water side. 
If both hot and cold faucets have low 
pressure, call your local water u  lity. 
If the low pressure is only on the hot 
water side, the primary causes are:

• 

 Melted heat traps or dip tube. Sol-
dering copper pipes while they are 
connected to the water heater can 
melt the heat traps inside the hot 
and cold water connec  ons or the 
dip tube (cold water side). Melted 
heat traps or a melted dip tube 
can restrict the fl ow of hot water. 
If that’s the case, replace the heat 
traps or dip tube.

• 

 Par  ally closed supply valve. Open 
the water heater’s supply valve fully.

Drips from T&P Relief 
Valve Discharge Pipe

A small amount of water dripping 
from the Temperature and Pressure 
(T&P) Relief Valve usually means the 
home’s water pressure is too high 
and/or you need a Thermal Expan-
sion Tank. See Step 1 in the Installa-

 on sec  on of this manual for more 

informa  on. 

A large amount of hot water coming 
from the T&P discharge pipe may be 
due to the tank overhea  ng. If the 
T&P relief valve is discharging large 
amounts of very hot water, turn the 
gas supply valve off  and call a quali-
fi ed person.

WARNING! Do not cap or plug the 

T&P Relief Valve or discharge pipe, 
and do not operate the water heater 
without a func  oning T&P Relief 
Valve—this could cause an explosion.

Water Pressure too High.

 High water 

pressure can cause the T&P Relief 
Valve to drip. Install a Pressure Re-
ducing Valve (PRV) on the main cold 
water supply line. Adjust the PRV to 
between 50 and 60 psi.

Thermal Expansion Tank. 

Install a 

Thermal Expansion Tank. If a Thermal 
Expansion Tank is already installed 
and the T&P Relief Valve discharge 
pipe drips, the home’s water pressure 
may be too high or the Thermal Ex-
pansion Tank may be defec  ve. Refer 
to the instruc  ons that came with 
the Thermal Expansion Tank for more 
informa  on.

Debris. 

In rare cases, debris can s  ck 

inside the T&P Relief Valve preven  ng 
the valve from sealing fully. In that 
case, the T&P Relief Valve discharge 
pipe will drip. You may be able to 
clear debris from the T&P Relief Valve 
by manually opera  ng the valve, 

allowing small quan    es of water to 
fl ush out the debris. See the label on 
the T&P Relief Valve for instruc  ons.

WARNING! When manually 

opera  ng the temperature-pressure 
relief valve, make sure that no one is 
in front of or around the discharge 
outlet.  The water may be extremely 
hot and could cause severe burns.   
Also ensure that the water discharge 
will not cause property damage.

 

If the water pressure is between 50 
and 60 psi, a Thermal Expansion Tank 
is installed and properly pressurized, 
and the valve has been cleared of any 
debris, and it s  ll drips, the valve may 
be broken—have a qualifi ed person 
replace the T&P Relief Valve.

Water Odor

Harmless bacteria normally present in 
tap water can mul  ply in water heat-
ers and give off  a “ro  en egg” smell. 
Although elimina  ng the bacteria that 
causes “smelly water” is the only sure 
treatment, in some cases, the stan-
dard anode rod that came with your 
water heater can be replaced with a 
special zinc anode rod which may help 
reduce or eliminate the odor. Contact 
a qualifi ed person.

NOTICE: 

To protect the tank, an anode 

rod must be installed in the water 
heater at all   mes or the warranty is 
void. 

In cases where the “ro  en egg” smell 
is very strong, you could increase the 
tank temperature to 140°F in order to 
reduce bacterial growth in the tank.

WARNING! Because higher 

temperatures increase the risk of 
scalding, if you set the thermostat(s) 
higher than 120°F, Thermosta  c 
Mixing Valves at each point-of-use 
are par  cularly important. 

Summary of Contents for GSL050-40

Page 1: ...on or service can damage the water heater your house and other property and present risks including fire scalding electric shock and explosion causing serious injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any p...

Page 2: ...t to cold water supply Hot water line T P relief valve Cold water shut off Dra hood T P discharge pipe Drain pan discharge pipe Metal drain pan Gas control valve thermostat Cold water line Gas supply shut off Vent pipe Drain valve Gas supply Sediment Trap ...

Page 3: ...avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situa on that if not avoided could result in minor or moderate injury NOTICE NOTICE indicates prac ces not related to physical injury WARNING If the informa on in these instruc ons is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline o...

Page 4: ...severe burns instantly resul ng in severe injury or death Feel water before bathing or showering To reduce the risk of scalding install Thermosta c Mixing Valves temperature limi ng valves at each point of use These valves automa cally mix hot and cold water to limit the temperature at the tap Mixing valves are available at your local plumbing supplier Follow manufacturer s instruc ons for install...

Page 5: ...er bu on if you suspect flammable vapor have accumu lated inside or outside the appliance Immediately call a qualified person to inspect the appliance Water heaters subjected to a flammable vapors inci dent will show a discolora on on the flame arrestor and require replacement of the en re water heater Improper installa on or an inadequate air supply can also cause the FVIR system to dis able the wate...

Page 6: ...odorless gas that is a by product of burning of fuels such as coal wood charcoal oil kerosene propane and natural gas Breathing excessive and abnormal amounts of carbon monoxide can cause carbon monoxide poisoning resul ng in serious injury or death This water heater must be supplied with adequate combus on air and must be properly vented to the outdoors Have a qualified person licensed plumber aut...

Page 7: ...ocal plumbing supplier with compres sion fi ngs that don t require soldering This kit includes two 12 flex water lines two compression fi ngs an 18 flexible gas line two nipples and thread sealant tape For homes with plas c pipe use threaded connectors suitable for the specific type of plas c pipe used CPVC or PEX cross linked polyethylene Do not use PVC pipe Non corrosive gas leak detec on solu on mad...

Page 8: ...le you will need to conduct the vent dra test on pages 23 24 when installa on is finished If there is not enough ven la on you will need to ven late with outside air Check for Chemicals Installa ons where corrosive chemi cals may be present require outside air Air for combus on and ven la on must be clean and free of corrosive or acid forming chemicals such as sulfur fluorine and chlorine Ven la on ...

Page 9: ...al or horizontal ducts B2 Determine type of ven la on There are several types of ven la on that can be used 1 Direct to outdoors 2 Ver cal ducts 3 Horizontal ducts 4 Single opening not recom mended must be at least 100 square inches Not appropriate for confined spaces smaller than 50 cubic feet per 1 000 BTU HR as calculated in sec on A or when ge ng air from another room 5 From a larger room insid...

Page 10: ...imension of no less than three inches All screens must have mesh or larger Moveable louvers must be locked open or interconnected with the equipment so that they open au toma cally during opera on Keep louvers and grills clean and free of debris or other obstruc ons B5 Check that air source is clean and free of chemicals Air for combus on and ven la on must be clean and free of corrosive or flammab...

Page 11: ...crawl spaces or any confined or inaccessible loca on Single wall vent pipe cannot pass through any interior wall Clearance to Combus ble Materials The vent pipe cannot pass through any ceiling floor firewall or fire par on Any part of the vent system must main tain the following clearances from any combus ble materials Single wall vent pipe must main tain a six inch clearance from combus ble materials...

Page 12: ...ype B double wall vent pipe Figure 9 Venting through a chimney with type B double wall vent pipe Gas Piping Gas piping must be installed accord ing to local and state codes or in the absence of local and state codes the Na onal Fuel Gas Code ANSI Z223 1 NFPA 54 current edi on NOTICE When installing gas piping apply pipe joint compound or thread sealant tape approved for fuel gases Figure 10 Gas Pi...

Page 13: ...at ing appliances when used to supply potable water Solar Installa on If this water heater is used as a solar stor age heater or as a backup for the solar system the water supply temperatures to the water heater tank may be in excess of 120 F A Thermosta c Mixing Valve or other temperature limi ng valve must be installed in the water supply line to limit the supply temperature to 120 F The unit mu...

Page 14: ...s water pressure Locate your home s Pressure Reduc ing Valve PRV on the main incoming cold water supply line and adjust the water pressure control to between 50 and 60 psi If your home does not have a Pressure Reducing Valve install a PRV on the home s main water supply line and set it to between 50 and 60 psi Pressure Reducing Valves are available at your local plumbing supplier BACKGROUND Over t...

Page 15: ...leaks and can shut off the water heater s water supply if a leak occurs Install a metal drain pan available at your local plumbing supplier under the water heater to catch condensa on or leaks from the piping connec ons or tank Most codes require and we recommend installing the water heater in a metal drain pan that is piped to an adequate drain The drain pan must be at least two inches wider than ...

Page 16: ...d on a metal or wood panel extending beyond the full width and depth of the water heater by at least 3 in 76 2mm in any direc on If the water heater is installed in an alcove or closet the en re floor shall be covered by the aforestated panel If your area is prone to earth quakes use special straps as required by local building codes NOTICE The state of California re quires bracing anchoring or str...

Page 17: ...erature Pressure T P Relief Valve discharge pipe You may be able to reuse the discharge pipe but do not reuse the old T P Relief Valve A new T P Relief Valve comes with your new water heater Figure 21 Removing the T P Relief Valve discharge pipe 10 Allow the vent pipe and dra hood to cool Once cooled disconnect the vent pipe from the dra hood You may need to support the vent pipe un l the new wate...

Page 18: ...covered by a wood or metal panel NOTICE Most codes require se ng the water heater in a metal drain pan piped to an adequate drain The drain pan helps avoid property damage which may occur from condensa on or leaks in the piping connec ons or tank The drain pan must be at least two inches wider than the diameter of the water heater Install the drain pan so the water level is limited to a maximum de...

Page 19: ...e discharge pipe must not be smaller than the pipe size of the T P Relief Valve The pipe must also be able to withstand 250 F 121 C without distor on Use only copper or CPVC pipe Do not use any other type of pipe such as PVC iron flexible plas c pipe or any type of hose Terminate the discharge pipe a maximum of six inches above a floor drain or outside the building Do not drain the discharge pipe in...

Page 20: ...he water heater for service or replacement con nect the water pipes with a coupling called a union We recommend using a dielectric type union available at your local plumbing supplier Dielec tric unions can help prevent corro sion caused by ny electric currents common in copper water pipes and can help extend the life of the water heater IF YOU HAVE COPPER PIPES If your home has copper water pipes...

Page 21: ...ator at the nearest hot water faucet This allows debris in plumbing system to be washed out of the pipes 2 Turn the cold water supply back on and fill the tank 3 Open a hot water faucet and allow the water to run un l it flows with a full stream 4 Let the water run full stream for three minutes 5 Close the hot water faucet and replace the aerator 6 Check inlet and outlet connec ons and water pipes f...

Page 22: ...ith large amounts of lint dust etc If so the air filter or flame arrestor located on the bo om of the water heater will need to be cleaned more o en Combus on Air Supply and Ven la on Adequate air supply for water heater and any other nearby gas appliances If the water heater is installed in a closet or other small enclosed space or within the living space of the house air supply openings needed Are...

Page 23: ... three seconds Wait 10 minutes between ligh ng a empts 7 A solid Status Light means the pilot was lit but is now off Release the gas control knob and wait 10 minutes Once the Status Light goes out repeat ligh ng steps 2 through 5 8 If the Status Light doesn t start flashing a er three ligh ng a empts turn the gas control knob to the OFF posi on and refer to the Troubleshoo ng No Hot Water sec on see...

Page 24: ...own as smelly water and can reduce the levels of bacteria that cause water borne diseases Water usage pa erns as well as heat from sources such as solar collectors ambient air and the pilot light can result in temperatures higher than the thermostat set point WARNING Higher temperatures increase the risk of scalding but even at 120 F hot water can scald see Table 1 Install Thermosta c Mixing Valve...

Page 25: ...water is simply not warm enough there are several possible causes Faulty Thermosta c Mixing Valve in a faucet or shower control check other faucets in the house for hot water Water heater s capacity too small or usage too high Reversed plumbing connec ons or melted dip tube usually found soon a er new installa on Plumbing leak Sediment or lime build up in the bo om of the tank Thermosta c Mixing V...

Page 26: ...f Valve or discharge pipe and do not operate the water heater without a func oning T P Relief Valve this could cause an explosion Water Pressure too High High water pressure can cause the T P Relief Valve to drip Install a Pressure Re ducing Valve PRV on the main cold water supply line Adjust the PRV to between 50 and 60 psi Thermal Expansion Tank Install a Thermal Expansion Tank If a Thermal Expa...

Page 27: ...Residen al Standard Gas Water Heater Use and Care Guide 27 TROUBLESHOOTING Residen al Standard Gas Water Heater Use and Care Guide 27 TROUBLESHOOTING ...

Page 28: ... to the drain valve and place the other end of the hose in a drain outside or in buckets Note that sediment in the bo om of the tank may clog the valve and prevent it from draining If you can t get the tank to drain contact a qualified person 5 Turn the cold water supply valve OFF 6 Open the drain valve on the water heater Figure 42 Draining the water heater 7 Also open a hot water faucet to help t...

Page 29: ... properly perform this visual inspec on or if the burner needs to be cleaned get help from a qualified person T P Relief Valve Maintenance Figure 45 T P Relief Valve Read and follow the opera ng and an nual maintenance instruc ons provided by the manufacturer of the T P Relief Valve yellow label a ached to T P Relief Valve Minerals in the water can form deposits that cause the valve to s ck or crea...

Page 30: ... thermostat thread a 4 sec on of gas pipe into the inlet and use it to turn the FVIR Safety System Opera onal Checklist TROU BLESHOOTING CHART gas control valve thermostat counterclockwise Do not use pipe wrench or equivalent to grip body Damage may result causing leaks Do not insert any sharp objects into the inlet or outlet connec ons Damage to the gas control valve thermostat may result Figure ...

Page 31: ...Residen al Standard Gas Water Heater Use and Care Guide 31 NOTES NOTES ...

Page 32: ...32 Residen al Standard Gas Water Heater Use and Care Guide NOTES NOTES ...

Page 33: ...Residen al Standard Gas Water Heater Use and Care Guide 33 NOTES NOTES ...

Page 34: ...34 Residen al Standard Gas Water Heater Use and Care Guide NOTES NOTES ...

Page 35: ... PILOT THERMOPILEASSEMBLY KIT 13 FINAL BURNER ASSEMBLY 14 MANIFOLD DOOR GASKET Pictured on next page REPAIR PARTS LIST Replacement parts may be ordered through your plumber or the local distributor Parts will be shipped at prevailing prices and billed accordingly NOTICE When ordering replacement parts have the following informa on ready Model and serial number Type of gas used Item number Parts de...

Page 36: ...ermopile and retainer clip Natural Gas or L P Item 13 Final burner assembly which contains the burner orifice manifold tube gasket door pilot tube thermopile manifold component block with retainer clip thermal switch and pilot assembly Natural Gas Low Nox or L P Item 14 Contains manifold door gasket Item 12 Item 13 L P Burner Item 14 Item 13 Natural Burner Lochinvar Water Heaters All Rights Reserv...

Reviews: