background image

EGS-I&S-01

4

NOTE: 

 Any claims for damage or shortage in shipment

must be filed immediately against the carrier by the
consignee.

IMPORTANT DECISIONS REQUIRED

BEFORE INSTALLATION

SIZING

1. Boiler DOE Heating Capacity –

 The Single-wall

Indirect water heater will provide the rated
performance only if used in conjunction with a
boiler with a DOE heating capacity (Boiler Output)
minimum of 220,000 Btu/hr. If the boiler has less
capacity, the output of the tank will be reduced. To
determine the approximate reduction in output from
the tank use the following formula:

New Rating = (maximum first hour rating) x

   Actual Boiler Output Capacity
Minimum Boiler Output Capacity

For example, what would the 140°F first hour rating be if
model EGS050 was installed with a boiler having a DOE
heating capacity of 180,000 BTU/hr?

Answer:

New Rating
=  297 gal/hr x (180,000 BTU/h)/(220,000 BTU/hr)
=  297 gal/hr x 0.818  = 

243 gal/hr

2. Circulator Sizing –

 Refer to Table below for the

corresponding pressure drop through the coil for
the given model. Calculate the pressure drop of
all straight pipe and fittings on the supply and
return of the water heater at the selected flow
rate. Add the piping/fitting pressure drop to the
pressure drop through the water heater coil. Select
a circulator that will provide an appropriate flow
rate at the combined pressure drop.

ADJUSTABLE AQUASTAT – 

The temperature may

be adjusted from 80°F to 160°F. The aquastat (thermostat)
was adjusted to 120°F before the heater was shipped from
the factory.  It is recommended that lower temperatures be
used to avoid the risk of scalding.  Refer to the “Warnings”
and the section on  SCALDING “under – Operating
Instructions.”  It is further recommended, in all cases, that
the water temperature be set for the lowest temperature that
satisfies your hot water needs.  This will also provide the
most energy efficient operation of the water heater and
minimizes scale formation.

Setting the water heater temperature at 120°F will reduce
the risk of scalds.  Some states require settings to specific
lower temperatures.

SACRIFICIAL ANODES—

Three sacrificial anode rods

have been installed in the tank head to extend tank life.  The
anode rods should be inspected annually to determine the
amount of sacrificial decay and replaced when necessary to
prolong tank life. Water conditions in your area will
influence the time interval for inspection and replacement
of the anode rod.  The use of a water softener may increase
the speed of anode consumption.  More frequent inspection
of the anode is needed when using softened (or phosphate
treated) water. Contact the plumbing professional who
installed the water heater or the manufacturer listed on the
rating plate for anode replacement information.

PRE-INSTALLATION

INSPECT SHIPMENT 

carefully for any signs of damage.

If damage is noted, do not install the product.  Contact the
shipper or manufacturer listed on rating plate.  All

 

equipment

is carefully manufactured, inspected, and packed. Our
responsibility ceases upon delivery of the packaged heater
to the carrier in good condition.

 

WARNING

Install a discharge line so that water discharged from the
temperature and pressure relief valve will exit within six
(6) inches above, or any distance below, the structural
floor and cannot contact any live electrical part. The
discharge line is to be installed to allow for complete
drainage of both the temperature and pressure relief valve
and the discharge line. The discharge opening must not
be subjected to blockage or freezing.  

DO NOT

 thread,

plug, or cap the discharge line. It is recommended that a
minimum clearance of four (4) inches be provided on
the side of the water heater for servicing and maintenance
of the combination temperature and pressure relief valve.

Do not place a valve between the combination

temperature and pressure relief valve and the tank!

NOTICE

Increasing the boiler DOE heating capacity above
220,000 Btu/hr will not increase the rating of the
water heater. Ratings are based on 180°F boiler
water.

Summary of Contents for EGS-I&S-01

Page 1: ...njury or substantial property damage CAUTION Indicates a potentially hazardous situation which if not avoided could result in death serious injury or substantial property damage NOTICE Indicates special instructions on installation operation or maintenance which are important but not related to personal injury hazards WARNING Indicates a potentially hazardous situation which if not avoided may res...

Page 2: ...required for this water heater This water heater meets or exceeds the ASHRAE IES 90 1b standards with respect to insulation and standby loss requirements CAUTION The maximum boiler water supply temperature to the indirect heat exchanger must not exceed 240 F 116 C WARNING It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating proper...

Page 3: ...Pressure Relief Valves and Vacuum Relief Valves The combination temperature and pressure relief valve must be marked with a maximum set pressure not to exceed the maximum working pressure of the water heater The combination temperature and pressure relief valve must also have an hourly rated temperature steam BTU discharge capacity not less than the hourly rating of the water heater The supplied c...

Page 4: ...le formation Setting the water heater temperature at 120 F will reduce the risk of scalds Some states require settings to specific lower temperatures SACRIFICIAL ANODES Three sacrificial anode rods have been installed in the tank head to extend tank life The anode rods should be inspected annually to determine the amount of sacrificial decay and replaced when necessary to prolong tank life Water c...

Page 5: ...ot water demand is satisfied This option provides maximum delivery of domestic hot water Priority is recommended when a Boiler net output is 100 000 Btu per hour or less or b When boiler output required to satisfy domestic hot water demand is at least 50 of the boiler output required to satisfy space heating demand or c When an interruption in space heating can be tolerated during a long domestic ...

Page 6: ...Expansion Tank If the water heater is installed in a closed water supply system such as one having a back flow preventer in the cold water line provide thermal expansion control Contact the water supplier or local plumbing inspector for additional information MOVE THE WATER HEATER TO A PERMANENT POSITION BY SLIDING OR WALKING WATER CONNECTIONS WARNING FAILURE TO INSTALL AND MAINTAIN A NEW LISTED T...

Page 7: ... system Pipe and fittings between the boiler and Single wall Indirect must be diameter or larger CAUTION Maximum boiler water supply temperature to the indirect heat exchanger must not exceed 240 F 116 C Figure 1 Water Boiler Piping with Zone Valves Figure 2 Water Boiler Piping with Circulators 2 For a space heating system that utilizes CIRCULATORS refer to Figure 2 The Single wall Indirect connec...

Page 8: ...s shown and screw the aquastat clamp securely in the well groove The aquastat acts as a thermostat for zone control and should be wired accordingly Refer to the boiler or zone control manufacturer s instructions if any additional wiring is required The control is factory set at 120 F and care should be made to not rotate this dial while wiring the control Once electrical connections are complete s...

Page 9: ...g WATER TEMPERATURE ADJUSTMENT 1 The aquastat controls the maximum water temperature in the tank The differential is a fixed 5 F with a 160 F maximum setting set at the factory to 120 F Table 4 details the approximate relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications 2 For the most ene...

Page 10: ...ecommended size as necessary Do not attempt to repair the valve as this could result in improper operation and a tank explosion In areas with poor water conditions it may be necessary to inspect the temperature relief valve more often than once a year If the temperature pressure relief valve on the heater discharges periodically or continuously it may be due to thermal expansion of water in a clos...

Page 11: ...ater electricity on for the zone containing the Single wall Indirect 4 Sediment Annual but harsh water quality may dictate more frequent service Depending on water conditions a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference in the supply and return lines See also Scale below Repeated flushing usually clears such material ...

Page 12: ...r or Clean or replace filter or strainer boiler supply strainer if used Aquastat set too high Lower aquastat setting See Operating Instructions Improper system plumbing Compare to plumbing in Water Connections Improper system wiring Compare to wiring in Electrical Connections Aquastat setting too low Adjust aquastat to higher setting See Operating Instruction Undersized boiler with no Rewire for p...

Reviews: