Lochinvar EcoShield SHW115-435CE User & Control Manual Download Page 4

 

1.0

 

USER GUIDE 

 

1.1

 

GENERAL REQUIREMENTS 

 

 

This equipment must be installed by a competent person, registered with a H.S.E. approved 

body.  All installations must conform to the relevant Gas Safety and Building regulations.  Health 

& safety requirements must also be taken into account when installing any equipment.  

 

 

A competent person must also undertake any alterations that require the gas train or flue system 

to be broken. 

 

 

Any interference with a sealed component is forbidden. 

 

 

Failure to comply with the above may lead to prosecution. 

 

 

Incorrect use may result in injury and will also invalidate the warranty 

 

1.2

 

PROCEDURE FOR LIGHTING 

 

1.

 

Ensure that the gas inlet appliance isolating valve is in the “off” position. 

2.

 

Press the power rocker switch, positioned on the back of the appliance to bring the equipment on. 

3.

 

Press the Enter/Reset button on the Smart System control panel to initiate the burner. 

4.

 

The combustion fan should ramp up to full speed to purge the combustion chamber and then drop back 

to half rate in order to light.  As the gas inlet appliance isolating valve is closed, the controls should go to 

a flame failure condition after four ignition attempts (SHW45-325CE – SHW115-435CE) or one ignition 

attempt (SHW145-435CE).  If the above occurs correctly, open the gas inlet appliance isolating valve 

and reset the unit by depressing the Enter/Reset button on the control panel. 

5.

 

The combustion fan will repeat the pre-purge procedure and attempt to light.  Once a flame is 

established, the LCD display will change to display the rate at which it is firing.  

 

1.3

 

PROCEDURE FOR SHUTTING DOWN 

 

To take the appliance out of service, the Enter/Reset button should be pressed.  If the appliance in to be shut 

down for a long period of time, the power supply should be isolated using the rocker switch on the back and the 

gas supply should be isolated at the gas inlet appliance isolating valve. 

 

1.4

 

TEMPERATURE ADJUSTMENT PROCEDURE 

 

The setpoint can be adjusted using the Up and Down buttons on the Smart System control panel.  Once the 

desired setpoint is displayed, the Enter/Reset button should be pressed to store the value. 

 

The setpoint should be adjusted to ensure that the water is stored at 60°C and distributed at 50°C within 1 (one) 

minute at all outlets.  Care is needed to avoid much higher temperatures because of the risk of scalding.  At 50°C 

the risk of scalding is small for most people, but the risk increases rapidly with higher temperatures and for longer 

exposure times.  The risk to young children and to those with a sensory or mobility loss will be greater.  Where a 

significant scalding risk has been identified, the use of thermostatic mixing valves on baths and showers should be 

considered to reduce temperature, these need to be placed as close to the point of use as possible. 

 

1.5

 

MAINTENANCE 

 

The SMART SYSTEM control has a built in timer that counts the time period, operating hours and burner initiation 

cycles since the unit was last maintained.  Once one of these preset values has been exceeded, the display will 

show 

SERVICE DUE

 every 5 seconds.  At this point, it is strongly recommended that a competent person, 

preferably appointed by Lochinvar Limited, carries out the necessary maintenance work. 

 

Details of the necessary maintenance work can be found in the Installation, Commissioning and Maintenance 

Instructions. 

 

 

 

Summary of Contents for EcoShield SHW115-435CE

Page 1: ...he EcoShield range High Efficiency Gas Fired Condensing Water Heaters User SMART SYSTEM Control Guide INS0014 Issue No 1 October 2010 SHW45 325CE SHW60 325CE SHW85 435CE SHW115 435CE SHW145 435CE Models ...

Page 2: ...2 ...

Page 3: ...NTERFACE PANEL 6 2 3 SEQUENCE OF OPERATION 7 2 4 STATUS DISPLAY SCREENS 8 3 0 USER SETTINGS 9 3 1 GENERAL 9 3 2 ENTERING THE USER CODE 9 3 3 MENU SET A GENERAL SETTINGS 9 3 3 1 WATER HEATER MODEL 9 3 3 2 USER CODE 9 3 3 3 TIME DATE 10 3 3 4 SOFTWARE VERSION 10 3 3 5 TEMPERATURE UNITS 10 3 3 6 NIGHT SETBACK TEMPERATURE 10 3 3 7 NIGHT SETBACK TIME 10 3 4 MENU SET C DATA LOGGING 11 3 4 1 TOTAL HRS RU...

Page 4: ... PROCEDURE FOR SHUTTING DOWN To take the appliance out of service the Enter Reset button should be pressed If the appliance in to be shut down for a long period of time the power supply should be isolated using the rocker switch on the back and the gas supply should be isolated at the gas inlet appliance isolating valve 1 4 TEMPERATURE ADJUSTMENT PROCEDURE The setpoint can be adjusted using the Up...

Page 5: ...UPPLY When installed as a conventionally flued appliance the room in which the appliance is installed must be ventilated Blocking these air vents may lead to severe injury serious property damage or death The area in which the appliance is installed should not be used to store any other materials 1 8 CONDENSATE DRAIN The condensate drain must not be blocked or modified in any way If fitted with a ...

Page 6: ...ROL 2 1 GENERAL The Lochinvar EcoShield user control interface gives information on set up system status and diagnostic data in words rather than codes 2 2 USER CONTROL INTERFACE PANEL FIGURE 2 1 USER CONTROL INTERFACE PANEL ...

Page 7: ...cycle is complete and the blocked drain and auto reset high limit are closed the control starts the 5 second trial for ignition by sending spark voltage to the spark electrode and opening the gas valve WHR IGNITION OUT 61 5C 5 If the control does not detect flame by the end of the trial for ignition the control performs a 10 second postpurge On the SHW45 325CE to SHW115 435CE models the control wi...

Page 8: ...ol does not detect the flue sensor SHORTED The flue sensor wires or the sensor itself has become grounded TANK C The control will display the stored water temperature the set point appears in brackets OPEN The control does not detect the tank sensor SHORTED The tank sensor wires or the sensor itself has become shorted Press the Next arrow key on the user control interface panel to access Screen 4 ...

Page 9: ... 7 times The display should now show Enter Menu Code 0704 6 Press the Enter Reset button The display should now show Enter Menu Code USER CODE 3 3 MENU SET A GENERAL SETTINGS After 2 seconds the screen will show A General B N A Pressing the Enter Reset button will access the General menu set From here the following sub sections can be accessed by moving the caret symbol to the appropriate line usi...

Page 10: ...tore the desired setting 3 3 6 NIGHT SETBACK TEMPERATURE Once the internal clock has been set correctly the night setback feature can be used to program a lower water temperature set point for water heating This feature is only used when a tank sensor is used The temperature range for this parameter is 0 C to 60 c The feature is turned off with a setting of 0 C The default value is 0 C To modify t...

Page 11: ...ON ATTEMPTS The Ignition Attempts option will show the number of times the water heater has attempted to fire since the counter was last reset 3 4 3 LAST 10 ERRORS The Last 10 Errors option will show the date time and fault description for the last ten errors that caused the boiler the stop The Up or Down button should be used to scroll through the errors 3 5 EXITING USER SETTINGS MODE To exit the...