background image

Copper-Fin

®

 Boiler Dimensions & Specifications

CBN-07  

(Replaced  CBN-06  3/10)

FG-10M-5/11-Printed in U.S.A.

Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000

www.Lochinvar.com

Standard Features

• 

81% Thermal Efficiency

• 

Electronic Temperature Control

• 

Fan Assisted Combustion

• 

Sealed Combustion Chamber

• 

Stainless Steel Burners

• 

Low NOx Operation Exceeds the most

Stringent Air Quality Requirements

• 

ASME Copper Finned Tube

Heat Exchanger

• 

160 psi Working Pressure

• 

Gasketless Heat Exchanger Design

• 

Pump Relay w/ Delay

• 

Down Stream Test Valve

• 

Referenced Gas Valves

• 

Loch-Heat Ceramic Tile 

Combustion Chamber

• 

Hot Surface Ignition

• 

Adjustable High Limit w/ Manual Reset

• 

ASME Pressure Relief Valve

• 

Temperature & Pressure Gauge

• 

Flow Switch

• 

24 Volt Control System

• 

BMS Terminal Strip

• 

Combustion Air Filter

• 

Freeze Protection

• 

10 Year Limited Warranty on Heat 

Exchanger (See warranty for details)

Optional Equipment

• 

Alarm Bell

• 

Contacts on any Failure

• 

Contacts for Air Louvers

• 

Cupro-Nickel Heat Exchanger

• 

High & Low Gas Pressure Switch 

   w/ Manual Reset

• 

Outdoor Reset Control

• 

Manual Reset Low Water Cut-Off

  w/  test

• 

Stack Frame

 MP

2

 Sequencer

Available Firing Systems

M9 

Hot Surface Ignition with 

     

Electronic Supervision (Standard)

M13 GE 

GAP/FM/CSD1

M7 California 

Code

Venting

• 

Outdoor Vent Cap

Registered under U.S. Patent # 5,989,020

For Ease In Ordering

By Model Number

C B   N   0 4 9 7   M 9

MODEL

Btu/hr

 INPUT

This boiler is a 495,000 Btu/hr,

natural gas Copper-Fin. 

It has M9 firing controls

NAT. GAS

FIRING

CONTROLS

Copper-Fin Heating Boiler 

 

 

 

Dimensions & Spec i fi ca tions

 Input 

 

 

Heating 

Net

  Model  Max  Thermal Capacity I=B=R 

 

 

 

 

 

 

 

  Gas  Vent  Shipping

 Number  MBH Efficiency  MBH 

MBH 

G    Conn.  Size  Weight

CBN0497 

495 

81% 

401 

349 

31-1/2”  45-1/4”  22-1/4”  12-1/2”    9-1/2” 

22-3/4”  29-1/2”  1-1/4” 

6” 

440

CBN0647 

645 

81% 

522 

454 

31-1/2”  56-3/4”  22-1/4”  12-1/2”    9-1/2” 

28-1/2”  29-1/2”  1-1/4” 

8” 

510

CBN0747 

745 

81% 

603 

524 

31-1/2”  64” 

22-1/4”  12-1/2”    9-1/2” 

32” 

29-1/2”  1-1/4” 

8” 

550

CBN0987 

985 

81% 

798 

694 

36” 

48-1/4”  33-1/2”  15-3/4”    8-1/2” 

  8-1/2”  33-3/4”  2” 

10” 

845

CBN1257 

1255 

81% 

1,017 

884 

36” 

58-1/2”  33-1/2”  15-3/4”    9-1/2” 

10-1/2”  33-3/4”  2” 

12” 

905

CBN1437  1435  81% 

1,162  1,010  36”  68-3/4” 33-1/2”  15-3/4” 10-1/2”  10-1/2” 33-3/4” 2” 

12”  1050

CBN1797 1795  81%  1,454  1,264 36”  82-1/4” 

33-1/2” 15-3/4” 

11”  11”  33-3/4” 

2”  14”  1193

CBN2067 2065  81%  1,673  1,455 36”  92-1/2” 

33-1/2” 15-3/4” 

11”  11”  33-3/4” 

2”  14”  1350

Notes:  Change ‘N’ to ‘L’ for LP gas models.    

 

Water connections for models CB 0497-747 are 2” NPT on 6-1/2” centers. 

 

No deration on LP models. 

 

 

 

Water connections for models CB 0987-2067 are 2-1/2” NPT on 11-1/4” centers.

Performance data based on manufacturer test results.

Reviews: