M02 – UTILITY UoM Default Range
P02.01 Language English English
Italiano
Francais
Espanol
Portuguese
Deutsch
P02.02 High backlight level % 100 0-100
P02.03 Low backlight level % 30 0-50
P02.04 Low backlight delay s 30 5-600
P02.05 Default page return s 60 OFF / 10-600
P02.06 Default pag W + kWh VL-L / VL-N …
P02.07 Default sub-page INST INST / HI / LO /
AVG / MD
P02.08 Display update time s 0.5 0.1 – 5.0
P02.09 Exported energy measure OFF OFF-ON
P02.10 Phase energy measure OFF OFF-ON
P02.11 Asymmetry measure OFF OFF-ON
P02.12 THD measure OFF OFF-THD
P02.13 Power unbalance measurement OFF OFF-ON
P02.14 Backlight flash when in alarm OFF OFF-ON
P02.15 Reactive power calculation TOT TOT-FUND
P02.05
– If set to OFF, the display always remains on the page where the user left it. If set to a value, after this time the display returns to the page set with P02.06.
P02.06
– Number of the page that the display returns to automatically once the time P02.05 since a button was last pressed has elapsed.
P02.07
– Type of sub-page that the display returns to after P02.05 has elapsed.
P02.09
– Enables the measurement and display of exported energies (generated towards the mains).
P02.10
– Enables the measurement and display of energies by individual phase.
P02.11
– Enables the measurement and display of voltage and current asymmetry.
P02.12
– Enables the measurement and display of voltage and current THDs (% Harmonic Distortion).
P02.13
– Enables the calculation and display of phase power unbalance.
P02.14
– When there is an alarm, the display’s backlight flashes to highlight the fault.
P02.15
– Selection of reactive power calculation method.
TOT:
the reactive power includes the harmonic contributions. In this case: P
reactive
2
= P
apparent
2
– P
active
2
FUND:
the reactive power includes the fundamental contribution only. In this case: P
reactive
2
≤
P
apparent
2
– P
active
2
. P
apparent
still includes the harmonic contribution (same value as TOT case).
In absence of voltage and current harmonics, both the calculation methods come to the same result and PF = cos
j
.
M03 – PASSWORD UoM Default Range
P03.01 Enable passwords OFF OFF-ON
P03.02 User level password 1000 0-9999
P03.03 Advanced level password 2000 0-9999
M04 – INTEGRATION UoM Default Range
P04.01 Integration mode Shift Fixed
Shift
Bus
P04.02 Power integration time min 15 1-60
P04.03 Current integration time min 15 1-60
P04.04 Voltage integration time min 1 1-60
P04.05 Frequency integration time min 1 1-60
M05 – HOUR COUNTER UoM Default Range
P05.01 Hour counters general enable ON OFF-ON
P05.02 Partial hour counter 1 enable ON OFF-ON-LIMx
P05.03 Hour counter 1 channel number (x) 1 1-4
P05.04 Partial hour counter 2 enable ON OFF-ON-LIMx
P05.05 Hour counter 2 channel number (x) 1 1-4
P05.06 Partial hour counter 3 enable ON OFF-ON-LIMx
P05.07 Hour counter 3 channel number (x) 1 1-4
P05.08 Partial hour counter 4 enable ON OFF-ON-LIMx
P05.09 Hour counter 4 channel number (x) 1 1-4
P03.01
– If set to OFF, password management is disabled and there is free access to settings and the commands menu.
P03.02
– With P03.01 active, value to specify to activate user-level access. See Password Access section.
P03.03
– As P03.02, with reference to advanced-level access.
P04.01
– Integrated measurement calculation mode selection.
Fixed
= The instantaneous measurements are integrated for the time set. Each time that the time set elapses, the integrated measurement is updated with the result of the latest integration.
Shift
= The instantaneous measurements are integrated for a time = 1/15 of the time set. Each time this interval elapses, the oldest value is replaced with the new value calculated. The integrated
measurement is updated every 1/15 of the time set, considering a time-shift window that includes the last 15 values calculated, equivalent in length to the time set.
Bus
= As fixed mode, but the integration intervals are dictated by synchronisation messages sent on the serial bus. (110)
P04.01
– Average (AVG) measurement integration time for active, reactive and apparent power.
P04.03, P04.04, P04.05
– Average (AVG) measurement integration time for the corresponding values.
P05.01
– If OFF, the hour counters are disabled and the hour counter measurement page is not displayed.
P05.02, P05.04, P05.06, P05.08
– If OFF, the partial hour counter (1, 2, 3 or 4) is not incremented. If ON, it is incremented when the energy meter is supplied. If linked to one of the internal variables (LIMn), it is
incremented only when this condition is true.
P05.03, P05.05, P05.07, P05.09
– Channel number (x) of any internal variable used in the previous parameter. Example: If the partial hour counter needs to count the time that a measurement is above a certain
threshold, defined by LIM3, program LIMx in the previous parameter and specify 3 in this parameter.