LK Systems Cq 1 Assembly Instructions Manual Download Page 5

5

EN.33.C.29.

Assembly instructions | LK Wireless Room Control Cq 1, 4 & 6 (NC)

Alternative 2

Changing the whole installation by reprogram-

ming the receiver unit as follows:

Change to cool (summer operation):

• 

Press the “Reset” button and the button for 

”Channel 3” at the same time.

• 

First release “Reset” followed by “Channel 

3”.

Change to heat (winter operation):

• 

Press the “Reset” button and the button for 

”Channel 4” at the same time.

• 

First release “Reset” followed by ”Channel 

4”.

NOTE: 

For the Cq 1 unit, the change is made on the room ther

-

mostat. 

Alarm

When a fault occurs, the indicator light begins to 

flash with an irregular time interval and a sound 

signal is heard. During signal disruption, the af-

fected channel will deliver approximately 30% 

heat output.

Temporary interruption

If no signal is received from the room thermostat 

(transmitter) for a period between 1 to 10 hours, 

the indicator light on the receiver unit will dis-

play short flashes, but no sound signal. Acknow-

ledgment of the alarm occurs automatically if the 

transmitter signal reoccurs.

Prolonged interruption

If no signal is received from the room thermostat 

(transmitter) for a period of more than 10 hours, 

the indicator light on the receiver unit will dis-

play short flashes and a sound signal is emitted. 

Acknowledgment of the alarm occurs automati-

cally if the transmitter signal is regained. In the 

event of a loss of power in the receiver unit, no 

programming will be affected. Operation will 

continue as normal once power is restored.

Pump control for Cq 4 and Cq 6

The last channels on the receiver Cq 4 (channel 4) 

and Cq 6 (channel 6) can start or stop a circula-

ting pump. However, Cq 4 becomes 3 channel 

and Cq 6, 5 channel receiver. Pump control can be 

arranged via an external relay for 24/230 V (relay 

not supplied by LK). The 24 Vside of the relay 

should be connected to terminals A and C of the 

channels. The channels have a time delay of 10 

minutes for pump control.

Range control of radio signal

To determine a connection’s maximum range, the 

following check can be carried out:

• 

First, carry out activation/memorizing as the 

instructions.

• 

Then push the “Reset” button on the recei-

ver unit at the same time as the button for 

“Channel 2”.

• 

First release “Reset” followed by the “Chan-

nel 2” button. The sound signal and the 

indicator light will now pulse for about 2 

seconds on, 8 seconds off.

• 

Next move the room thermostat far enough 

away from the receiver unit that the pulses 

almost stop. This is the maximum distance 

for radio connection.

• 

Finish the check by pressing “Reset” on the 

receiver unit.

The room thermostat returns to normal operation 

mode after a short time. Other channels are not 

affected by the check. If the connection is insuf-

ficient, the radio signal can be strengthened with 

LK Repeater Cq. See separate section, LK Repea-

ter Cq.

Heating & Cooling

The equipment is constructed so that it can be 

used to heat(under floor heating) and cool. The 

functions are changed manually. When supplied, 

the components are set for heat. Switching to cool 

can be done in two ways.

Alternative 1

Change all room thermostats by moving the 

mains switchA to the upper position.

Summary of Contents for Cq 1

Page 1: ...ximum of 4 control zones channel 1 4 LK Cq 6 for a maximum of 6 control zones channel 1 6 The receiver unit functions along the same prin ciples but the Cq 1 unit which only has one re ceiver channel...

Page 2: ...e ac tuators Cq 4 and Cq 6 receiver units can operate a maximum of 16 actuators When connecting two or more actuators to the same channel the connections must be only to the double circuit boards a ch...

Page 3: ...the indicator light will come on Activating the room thermostat Press and hold the lower black button B Briefly press the upper black button C When the indicator light D is lit release the lower butto...

Page 4: ...ment dial the indicator light on the receiver s channel will be lit or switched off respectively within approx imately 30 seconds Dial towards maximum temperature the light on the receiver unit comes...

Page 5: ...normal once power is restored Pump control for Cq 4 and Cq 6 The last channels on the receiver Cq 4 channel 4 and Cq 6 channel 6 can start or stop a circula ting pump However Cq 4 becomes 3 channel a...

Page 6: ...minutes the output will return to its correct position Any radio con nection established will not be affected Valve exercising The actuator disconnects once a day for 3 mi nutes and opens the valve o...

Page 7: ...tes total on and off time Measurement interval Approximately 10 minutes Type Heat Cool Valve exercising Once a day for 3 minutes can be switched off BR1 Temperature sensor NTC Transfer frequency 868 M...

Reviews: