Littelfuse Industrial Shock Block SB5000 Series Manual Download Page 16

 

SB5000 Industrial Shock Block

 Page 

12 

  Rev. 

1-B-101821 

 
 

 

4

.  

UL 943C R

EQUIREMENTS 

  The  following  sections  contain  excerpts  from  the  
UL 943C

(1)

 Standard for Class C and D applications.  For 

EGFPD models, only Section 4.1 applies where selectable 
trip  levels  from  6  to  100  mA  are  permitted  
(20 mA is the only allowed trip level for GFCI devices in 
NEC applications). 

 
4.1  T

RIP 

T

IME

 

  Class  C  and  Class  D  GFCIs  shall  be  capable  of 
interrupting the electric circuit to the load when the fault 
current to ground (

I

) is within the range of a minimum of 

20  mA  through  a  maximum  of  (110%  of  the  rated 
voltage/500  Ω)

  A

  within  the  time  interval  (

T

)  in 

accordance with the relationship: 
 

 

  Where: 
 

 T 

is expressed in seconds, and  

  I

 is expressed in mA 

  Except that 

T

 is not required to be less than 20 ms. 

 
  The tripping threshold of these GFCIs shall be in the 
range of 15 to 20 mA.  
  Fig. 14 shows the Class-A GFCI maximum-trip-time-
versus-current curve defined by UL 943 (with the above 
formula); UL 943 also defines a limit to the formula, with 
a  minimum  required  trip  time  (or  fastest  trip  speed)  of  
20  ms,  which  occurs  at  about  300  mA  of  ground-fault 
current (

I

) per the formula.  Class C and D GFCIs must 

operate within this same curve, except that their operating 
threshold is 15 to 20 mA (non-adjustable).  See Fig. 15.  
The  SB5000  EFGPDs  described  in  this  manual  also 
operate  within  the  Class-A  formula,  but  have  a  6-  to  
100-mA threshold setting range. 
 

4.2  G

ROUNDING 

C

IRCUIT

 

  The equipment grounding circuit of the circuit shall be 
sufficiently low impedance that, should a fault to ground 
occur, the voltage resulting across the grounding circuit 
shall  not  exceed  150  V.    The  size  of  the  grounding 
conductor  required  for  a  circuit  shall  be  determined  by 
calculating the resistance using the following formula and 
converting that value to a wire gauge based on the length 
of the equipment grounding conductor: 
 

  

 
  Where: 
 

 

R

G

  is  the  resistance  of  the  equipment  grounding 

conductor 
 

R

U

 is the resistance of the ungrounded conductor, and 

 

V

LG

  is  the  RMS  value  of  the  supply  line  to  ground 

voltage 
  Refer to UL 943C Appendix A for a sample calculation 
of grounding conductor size. 
 

4.3  G

ROUNDING

 M

ONITOR

/I

NTERRUPTER

 

  A  GFCI  shall  be  capable  of  detecting  and  causing 
interruption  of  the  circuit  under  both  of  the  following 
conditions: 
a) An open grounding circuit, and 
b) Impedance in  the  grounding  circuit  that  would  allow 
more than a 150 volt drop in the grounding circuit. 

(1)

  Excerpts  from  UL  943C  are  the  property  of 

Underwriters Laboratories Inc. 

 

FIGURE 12.  Class-A GFCI Curve. 
 

FIGURE 13.  Class-C and -D GFCI Curve. 

T

 =

1.43

20

I

( )

10

0.1

20 ms

0.01

0 6

100

200

300

TIME (s)

CURRENT (mA)

1

10

0.1

20 ms

0.01

0

20

100

200

300

TIME (s)

CURRENT (mA)

1

Summary of Contents for Industrial Shock Block SB5000 Series

Page 1: ...Tel 1 800 832 3873 E mail relays littelfuse com www littelfuse com SB5000 SB5000 MANUAL INDUSTRIAL SHOCK BLOCK REVISION 1 B 101821 Copyright 2021 by Littelfuse Inc All rights reserved...

Page 2: ...SB5000 Industrial Shock Block Page i Rev 1 B 101821 This page intentionally left blank...

Page 3: ...irements 11 4 UL 943C Requirements 12 4 1 Trip Time 12 4 2 Grounding Circuit 12 4 3 Grounding Monitor Interrupter 12 5 Troubleshooting 13 6 Technical Specifications 14 6 1 SB5032 Series 14 6 2 SB5060...

Page 4: ...SB5000 Industrial Shock Block Page iii Rev 1 B 101821 This page intentionally left blank...

Page 5: ...priate for many industrial and commercial applications Special purpose SB5000 GFCIs Class C or Class D can be used in the following applications 3 Phase Grounded neutral systems where voltage to groun...

Page 6: ...y points predrilled Appropriate holes must be made in the enclosure and fitted with NEMA 4X rated and IP69K rated when required fittings for the installation of all conductors Space is left near the b...

Page 7: ...d at the GC and REF terminals The termination device should remain installed at the GC and REF terminals if the load ground connection monitoring feature is not required See Fig 3 2 6 Trip Status Term...

Page 8: ...SB5000 Industrial Shock Block Page 4 Rev 1 B 101821 FIGURE 3 SB5060 x11 0 Model Lid not shown...

Page 9: ...SB5000 Industrial Shock Block Page 5 Rev 1 B 101821 FIGURE 4 SB50xx Lid closed...

Page 10: ...SB5000 Industrial Shock Block Page 6 Rev 1 B 101821 FIGURE 5 SB50xx Outline and Mounting Details...

Page 11: ...tions FIGURE 7 1N5339B Zener Diode and SE TA6 SM Termination Devices 69 9 2 75 G GC TERMINATION MUST BE INSTALLED AT LOAD G 1N5339B 0 25 28 UNF SE TA6 SM G GC 35 0 1 38 250 9 84 LENGTH OF 14 AWG YELLO...

Page 12: ...DIMENSIONS IN MILLIMETRES INCHES 2 TERMINAL BLOCK SCREWS 6 32 x 0 25 3 MOUNTING SCREWS M4 OR 8 32 4 ENCLOSURE IS ELECTRICALLY CONNECTED TOTERMINAL G 5 CAN BE IMMERSED IN GLYCOL NOTE 2 4 0 0 16 50 8 2...

Page 13: ...more conditions may have caused a trip If the GF TRIP LED is flashing the SB5000 has detected an undervoltage overvoltage chatter or temperature limit condition See Table 1 and Sections 3 5 and 3 6 3...

Page 14: ...tter Detection trip Undervoltage trip or Overvoltage trip will require a manual reset after returning to a normal state 3 4 INPUT CONNECTION The SB5000 electronics are supplied from input phases A and...

Page 15: ...43C load ground monitor requirements For EGFPD and GFCI Class A models load ground connection monitoring is optional 3 10 UL 943 SELF TEST AND UL 1998 REQUIREMENTS The 2015 revision to the UL 943 stan...

Page 16: ...5 to 20 mA non adjustable See Fig 15 The SB5000 EFGPDs described in this manual also operate within the Class A formula but have a 6 to 100 mA threshold setting range 4 2 GROUNDING CIRCUIT The equipme...

Page 17: ...s within acceptable limits and press RESET ON OFF OFF ON RED Load Ground Connection Open Check load ground pilot wire and termination device 1 ON OFF OFF FLASH RED 1 S 1 L GC Short detected Check resi...

Page 18: ...c Option Voltage 3 PH 3 wire no neutral 60 Hz 2 480 Vac 10 15 Current AC 1 60 A AC 3 60 A Breaking Capacity 5 x 60 A Making Capacity 5 x 60 A Power AC 3 40 hp 600 Vac Option Voltage 3 PH 3 wire no neu...

Page 19: ...9K Polycarbonate Lockable Dimensions Height 285 7 mm 11 2 in Width 244 3 mm 9 6 in Depth 119 6 mm 4 7 in Shipping Weight All Models 4 5 kg 10 lb Environment Operating Temperature UL Rating 35 to 66 C...

Page 20: ...ermination Assemblies 1 1N5339B 5 W Axial Lead Termination Device SE TA6 50 W Termination Assembly SE TA6 SM 50 W Stud Mount Termination Assembly SE TA6ASF WL 12 W Small Format Termination Assembly wi...

Page 21: ...ctober 18 2021 1 B 101821 02 01 1 23 May 28 2021 1 A 052821 00 MANUAL REVISION HISTORY REVISION 1 B 101821 UL approval for Class A and EGFPD models REVISION 1 A 052821 Initial release PRODUCT REVISION...

Reviews: