LITHONIA LEM EMERGENCY DRIVER
LEM_DRIVER.EPS
AC (NORMAL)
DRIVER
LEM
EMERGENCY DRIVER
LED
LOAD
WHITE
COMMON
AC INPUT (120 TO 277V)
SWITCHED OR
UNSWITCHED
HOT
BLUE (+)
BLUE / WHITE (-)
YELLOW (+)
YELLOW / BLACK (-)
LED INPUT(+)
LED INPUT (-)
LED OUTPUT (+)
LED OUTPUT (-)
UNIT
CONNECTOR
TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.
MATE UNIT CONNECTOR AFTER INSTALLATION IS
COMPLETE AND AC POWER IS SUPPLIED
WALL SWITCH
WHITE
BLACK
VIOLET (+)
BROWN
BROW
N
VIOLET
(+
)
INSTALLATION INSTRUCTIONS
WARNING:
To prevent high voltage from being present on the YELLOW and YELLOW/BLACK output leads prior
to installation, the unit connectors must be open (disconnected.) Do not join the unit connector until installation is
complete and AC power is supplied to the emergency driver.
CAUTION: Before installing, make certain the A.C. power is off and the LEM Emergency Driver unit
connector is disconnected.
Model
LEM04 A, LEM04 B
LEM08 A, LEM08 B
Output Wattage
4 watts (approx.)
8 watts (approx.)
TABLE A: Model Wattage
2. Mounting the LEM Emergency Driver
For LEM04 A and LEM08 A: The
LEM Emergency Driver
should be mounted on or nearby the fixture above the
ceiling. Route the flexible conduit to the fixture or junction box to make the necessary connections.
For LEM04 B and LEM08 B: Mount the
LEM Emergency Driver
in the driver/lamp compartment or enclosed
wireway so the wire leads are not exposed at least 1/2” away from the normal driver. Refer to Illustrations 1 and 2.
When battery packs are remote mounted, consult Customer Service for the maximum allowable distance between
the battery pack and the load.
Illustration 1
NOTE: Position the
Test Switch/Indicator
so that it can be seen after installation.
Illustration 2
VIOLET (+)
BROWN
FIXTURE
TEST SWITCH / INDICATOR
7/8" BUSHING
FIXTURE
CHANNEL COVER
PLASTIC TUBE
TBTS
FIXTURE LENS
LEM UNIT
OBSERVE PROPER POLARITY
TEST SWITCH / INDICATOR
LEM UNIT
3. Wiring
Refer to the wiring diagram below for the appropriate wiring of the LED load and driver. Install in accordance with
the National Electrical Code and local regulations. For additional wiring diagrams consult Customer Service.
1. System Compatibility
The
LEM Emergency Driver
can be used with most LED loads
that operate at 20-50 VDC.
1. The
LEM Emergency Driver
series has been evaluated to
and found compliant to UL standard 924. The as-installed
performance of system must meet or exceed all Federal,
State, and Local code requirements.
2. Approximate output power of the LEM Emergency Driver is
based on the model (See
Table A)
and of the
forward voltage required to operate the LED array.
3. See
Page 4
for methods to calculate emergency light levels.