Installation Instructions
HFM  Hazardous Location Floodlight
Class 1 Div 2
Groups A, B, C, D

Lithonia Lighting Outdoor

One Lithonia Way,  Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com

  Part  Number: RJ5210151  Rev B

Revision Date: 6/16/10

©2001 Acuity Brands Lighting, Inc.
All Rights Reserved. Rev. 06/10

Delivery: Upon receipt of fixture and accessories (packed separately), thoroughly
inspect  for any freight damage.  All damage should be reported to the delivery
carrier.  Compare the catalog description listed on the packing slip with the
fixture label on the inside of the housing to be sure you have received the
correct merchandise.

Lamp Installation:  Loosen the 2 closing screws, hinge door assembly forward to access lamp compartment .   Verify that the lamp source
and wattage corresponds with the fixture and ballast label.  HID -Screw the lamp securely into the socket, back it out one or two turns,
and tighten securely again.  This procedure properly seats the lamp in the socket.    Close door using the standard closing screws.

Troubleshooting:  If this fixture fails to operate properly, check to make sure:  The proper lamp is installed correctly.     • The fixture is
wired correctly.     • The lamp is not faulty.     • The fixture is grounded correctly.     • The line voltage at the fixture is correct.

Multi-tap Ballast (TB):    The multi-tap ballast will be prewired for 277V at the factory.  First determine the correct line voltage.  Then
select the corresponding fixture voltage lead, remove the crimped cap and connect to the supply voltage lead.  The fixture lead marked
COM should be connected to the neutral supply lead for 120 or 277.  For 208 or 240, connect the other incoming hot leg to the fixture lead
marked "COM".  Be sure to cap off all unused fixture leads individually.

The standard fixture comes with a yoke mounting bracket which can easily be mounted to a variety of accessory mounting hardware.

1. Mount floodlight to desired mounting hardware.

2. Loosen the 2 captive screws in front housing and allow fixture to hinge open.

3. Loosen the two screws and remove optical assembly.

4. Secure appropriate conduit fitting (not provided) to fixture hub provided.  Make wire connections.  For multi-tap ballast, refer to
instructions below.

5. Replace optical assembly with two screws.

6. Lamp fixture per instructions below.  Close front housing, and tighten the 2 captive screws.

OPERATING TEMPERATURE:

    The operating temperature

“T-Code”, listed for this luminaire is based on the following
bulb sizes.  Use of any other than these may result in a
higher operating temperature.

Lamp Type

Wattage

Bulb Size

Base

High Pressure Sodium

100

ED 17

Med

High Pressure Sodium

150

ED 17

Med

Metal Halide

150

ED 17

Med

Metal Halide

175

ED 17

Med