PAGE: 2 of 2
TOP & SIDE MOUNT INSTALLATION:
1. Remove lens on bottom of fi xture, set aside.
2. Remove EXIT stencil from housing, set aside.
3. Place screws (provided) in holes on the canopy.
4. Remove the desired mounting hole plug located on the frame of the sign. For ceiling mount, hole plug will be located on the top of the
housing. For wall mount, hole plug will be located on the side of the housing.
5. Route EXIT input wires through mounting hole of the housing, through the mounting canopy and through the center of the metal mount-
ing plate. Dress wires carefully through housing.
6. Make wiring connection. For 120V, use black and white wires and for 277V, use red and white wires. WARNING: Properly insulate the
unused lead with a wire nut (provided) or other approved means.
7. Push wire connections into the J-Box. Secure mounting plate to junction box (hardware not included).
8. Secure the canopy to the steel mounting plate with screws installed in step 2.
9. Remove proper chevron(s) as required. When removing chevrons it may be helpful to remove the color diffuser panel to allow easier
access to the chevrons. If removing color diffuser panel it is important to remember to reinstall the diffuser panel once chevron(s) have
been removed.
10. Connect battery only after continuous AC power can be provided to the unit.
11. Secure face plate(s) to the housing.
12. Install lens removed in step 1 to bottom of fi xture.
13. Apply continuous AC power and press “TEST” button to check operation.(See operation (battery back-up) for testing procedures)
OPERATION (Lightbar Adjustment):
1. Rotate the light bar to set the direction of the light output by using a fl at head screwdriver to turn the knob located next to the test switch
on the side of the unit.
OPERATION (Battery Backup):
1. Apply AC power to the unit. The LED indicator will be RED.
2. After the battery has been left to charge for 24 hours, test the unit by pushing the switch. The LED indicator turns OFF and the LED
board stays ON.
3. When the switch is released, the LED indicator turns back to RED and the LED board stays ON.
MAINTENANCE:
Caution: Always turn OFF AC power to the equipment before servicing. Servicing should be performed only by a qualifi ed service technician.
Use only MANUFACTURER supplied replacement parts.
1. BATTERY: The battery supplied in this equipment requires no maintenance. However, it should be tested periodically and replaced when
it no longer operates the connected sign for the duration of a 30-second or 90-minute test. The battery supplied in this equipment has a
life expectancy of 5 years when used in a normal ambient temperature of 72°F.
WIRING DIAGRAMS
:
One Lithonia Way, Conyers GA 30012
Phone: 800-334-8694
www.lithonia.com
Part No. EMCSA00805 Rev.
E
201
7
.0
6
.
20
High output with remote capacity