Insert the adapter plate with
XLM 35
into the housing bottom of the
SCU 835
and fix it clockwise into
the threaded sockets with the provided
M5x8
and
M3x8
fastening screws. Please note the corresponding
torque (
M5x8
with
2.2 Nm
resp.
M3x8
with
1.1 Nm
).
Attention
The e
X
tended
L
ine
M
odule
XLM 35
is neither an article of the manufacturer nor included in the scope of
delivery of d-LIST systems.
For the assembly of the components, the corresponding adapter plate, including the necessary mounting
material, is required. This is optionally available from the manufacturer of the d-LIST system.
6.14
MultiLine-SpecialFireDetector ML-SFD
The sensor control unit
SCU 835
can communicate with the Securi-
M
-Line of the IP-Integral fire
alarm control panels as well as the SecuriFire series. In this case an optional adapter plate for
the
ML-SFD
must
be installed in the housing bottom of the device and connected with the con-
nector at
P503
of the mainboard
MB SCI 835
. The following information can be transmitted to
the
FACP
via the Securi-
M
-Line (ring line):
Alarm status per cable port
I
/
II
for maximum
32
alarm zones.
Fault status per cable port
I
/
II
for maximum
32
fault zones.
Pre signal status per cable port
I
/
II
for maximum
32
pre-signal zones.
Reset.
Mounting the adapter plate for
ML-SFD
:
The sensor control unit
SCU 835
has to be opened for mounting the adapter plate.
Insert the provided combi-screws
M3x8
on the back of the adapter plate through the marked holes and fix
the spacers
M3x10
clockwise on the front as shown.
60T328-02-LI-en / 29.01.2021
LISTEC GmbH
Page 67/112
Fig. 145: Insert the adapter plate with
XLM 35
into
SCU 835
Fig. 146: Fix the adapter plate
Fig. 147:
ML-SFD
interface
Fig. 148: Insert the combi-screws
M3x8
Fig. 149: Fix the spacers
M3x10
PZ1
6
PZ1 / PH2