LinkAYL LK-CP62 Series Quick Start Manual Download Page 1

 

LK

CP62X

 

SERIES

 

CONTROL

 

PANEL

 

 

 

LK

CP621

                           

LK

CP622

                         

LK

CP625

   

 

Feature

 

 

Controller

 

is

 

used

 

in

 

window

 

opener,

 

curtain

 

motor

 

and

 

door

 

opener

 

24V

 

DC

 

motor

 

control

 

 

Power

 

indicator/reset,

 

Open/Stop/Close

 

&

 

channel

 

selection

 

buttons

 

with

 

backlight

 

 

Single

 

Channel,

 

dual

 

Channel,

 

5

 

Channel

 

and

 

cascade

 

controls

 

 

Cascade

 

control

 

can

 

be

 

cascaded

 

with

 

LK

UP2,

 

LK

FP3,

 

LK

CP6/CP7/CP8

 

that

 

achieves

 

windows

 

of

 

zone

 

control

 

and

 

group

 

control

 

 

Can

 

handle

 

external

 

input

 

signal

 

of

 

Manual

 

Switch,

 

Remote

 

Control,

 

Timer

 

Smoke/Gas/

 

Rain

 

/Temperature

 

&

 

Humidity

 

Sensors

 

 

Output

 

fire

 

feedback

 

signal

 

to

 

fire

 

centre

 

 

Compatible

 

with

 

all

 

Linkayl

 

remote

 

 

Inching

 

mode

 

and

 

continued

run

 

mode

 

settable

 

 

With

 

stroke

 

memory

 

function

 

 

Built

in

 

switching

 

power

 

supply

 

30A

 

/40A

 

 
 

 

Model

 

List

 

Model

 

Power

(W)

 

Control

 

Method

 

Input

 

Volt

 

(V)

 

Output

 

Volt

 

(V)

 

Temp

(

)

 

Size

 

(mm)

 

LK

CP621

30A

720

 

1

 

way

 

single

AC110/AC230

DC24

 

DC12

 

20

 

 

+65

292(L)

 

258(W)

87(H)

 

LK

CP621

40A

960

 

LK

CP622

30A

720

 

2

 

way

 

single/group

LK

CP622

40A

960

 

LK

CP625

30A

720

 

5

 

way

 

single/group

LK

CP625

40A

960

 

Application

 

Model

 

LK

SCE

D

LK

LCD

LK

TC

LK

L

LK

L

S

LK

L38A

 

600N/1000N

LK

L38A

 

1500N

 

LK

CP621

30A

25

 

15

 

7

 

15

 

15

 

15

 

10

 

LK

CP621

40A

33

 

20

 

10

 

20

 

20

 

20

 

13

 

LK

CP622

30A

25

 

15

 

7

 

15

 

15

 

15

 

10

 

LK

CP622

40A

33

 

20

 

10

 

20

 

20

 

20

 

13

 

LK

CP625

30A

25

 

15

 

7

 

15

 

15

 

15

 

10

 

LK

CP625

40A

33

 

20

 

10

 

20

 

20

 

20

 

13

 

 

 

 

Summary of Contents for LK-CP62 Series

Page 1: ...eedback signal to fire centre Compatible with all Linkayl remote Inching mode and continued run mode settable With stroke memory function Built in switching power supply 30A 40A Model List Model Power W Control Method Input Volt V Output Volt V Temp Size mm LK CP621 30A 720 1 way single AC110 AC230 DC24 DC12 20 65 292 L 258 W 87 H LK CP621 40A 960 LK CP622 30A 720 2 way single group LK CP622 40A 9...

Page 2: ...el 5 Terminals Symbol Description Symbol Description L AC Live wire FSO Fire feedback COM N AC Null wire FOO Fire feedback NO E AC Earth wire FOC Fire feedback NC 24V DC24V Input 24V Output DC24V 24V DC24V Input FSI Fire signal input M Motor DC24V COM COM signal M Motor DC24V S Slave control up MU Manual switch up S Slave control down MS Manual switch 12V Output DC12V MD Manual switch WRD Rain sen...

Page 3: ...button the windows open LED turns on turns off after 5 seconds Press DOWN button the windows close LED turns on turns off after 5 seconds Press STOP button the motors stop LED turns on LED turns off after 1 second Single Channel Control Press channel selection keys the corresponding LED lights channel selected Press the channel selection button again or no operation on controler thin 10 seconds LE...

Page 4: ...ded Control Can be used as a master controler a slave controler or play a dual role of master slave controler at the same time As a master controler connects to the motors or slave controlers to drive them As a slave controler input terminals S and S are connected to the output terminals M and M of the master controler to receive the instructions to drive motors or drive the motors independently P...

Page 5: ...ed in case the controler is powered down or reset When closing the window the output time is 5 minutes Installation instruction Please read the following instructions carefully before installing this product Installing this product must comply with the effective local electricity specifications The control system must be installed by the professional The main power must be cut off before wiring to...