15
Size AxB
Number
of blades
Weight [kg]
Sef [m
2
]
Actuating
Mechanism
Size AxB
Number
of blades
Weight
[kg]
Sef [m
2
]
Actuating
Mechanism
1100x200
1
29.1
0.1505
BEN
1200x200
1
30.8
0.1647
BEN
x250
2
34.0
0.1791
BEN
x250
2
35.9
0.1960
BEN
x300
2
35.9
0.2321
BEN
x300
2
38.0
0.2540
BEN
x350
2
37.9
0.2851
BEN
x350
2
40.1
0.3120
BEN
x400
2
39.9
0.3381
BEN
x400
2
42.2
0.3700
BEN
x450
3
47.2
0.3668
BEE
x450
3
49.8
0.4014
BEE
x500
3
49.2
0.4198
BEE
x500
3
51.9
0.4594
BEE
x600
3
53.2
0.5258
BEE
x600
3
56.1
0.5754
BE
x700
4
59.9
0.6074
BE
x700
4
63.2
0.6647
BE
x800
4
63.8
0.7134
BE
x800
4
67.4
0.7807
BE
x900
5
70.5
0.7950
BE
x900
5
74.5
0.8700
BE
x1000
5
74.5
0.9010
BE
x1000
5
78.7
0.9860
BE
x1100
6
81.1
0.9826
BE
x1100
6
85.8
1.0753
BE
x1200
6
85.1
1.0886
BE
x1200
6
90.0
1.1913
BE
Tab. 3.2.1. Weights and effective area cross section
lindab | we simplify construction
Smoke Control Damper
SDJR-S
Lindab reserves the right to make changes without prior notice
Last modified: 2021-09-03
Rev: 2021-03-26
If is used the communication and supply device BKNE230-24, the weight is higher by 0,68 kg.
Example, how to calculate effective area and size of SDJR-S damper [AxB], when knowing air volume in [m³/s] or [m³/h] on damper. Maximum
allowed air velocity on SDJR-S is 12 [m/s].
Formula:
Sef = Q / v
Q … air volume [m³/s]
Sef … effective free area of damper [m²] v … air velocity on damper [m/s]
Example:
Air volume needed is 26000 m³/h
26000 / 3600 = 7,222 m³/s
7,222 / 12 = 0,602 m² is min. effective free area [Sef]
Find the value Sef in the table 3.2.1. The effective are has to be the same or bigger. There will be more options of damper, sizes AxB.