3
Fire Batt (Weichschott) sealings
EI 120 S
(300 Pa)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
Rigid w
all
EI 120 S Installation within vertical rigid wall with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
Fle
xible w
all
EI 120 S Installation within vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall rock wool minimum density 100 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i
↔
o)
W
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
Floor
EI 120 S Installation within floor with Fire Batt (Weichschott) sealing
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i
↔
o)
W
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600
B X H
min 100 X 200
max 800 X 600