background image

6

Pressure 
[Pa]

Air flow [l/s]

300

10

12

14

16 18 20

22

24

26

30

32

34

36

38

40 45 50 55 60 65

28

200

100

150

90

80

70

60

50

4

5

6

7

8

9

10

15

20

25

30

35

40

45 50

60

70

80 90 100

Number open Nozzles

Service & Maintenance          Fasadium 

Lindab reserves the right to make changes without prior notice

2022-09-30

Lindab reserves the right to make changes without prior notice

2022-09-30

lindab  |  for a better climate

 

 

2.2.2 Calculating the airflow

 

– After measuring the static nozzle pressure, calculate the air flow per nozzle: 

q=0.0622∙√P 
q = air flow per nozzle 
P = static nozzle pressure 

 

– After finding the air flow per nozzle, find the needed number of open nozzles: 

tot

/q=n 

open

 

tot

 = total air flow 

open

 = open nozzles 

 

– Alternatively, read off the needed number of nozzles in the diagram below.

Summary of Contents for Fasadium

Page 1: ...thout written permission are forbidden is the registered trademark of Lindab AB Lindab s products systems product and product group designations are protected by intellectual property rights IPR lindab for a better climate LindabFasadium Service Maintenance ...

Page 2: ...tion specialist Lindab s chilled beams can beneficially be used together with Lindab s Safe duct systems 1 5 Connection description water Flow indication arrows are shown on the inlet and return pipes in order to assist the installer If the control valves have been ordered separately a special direction of the flow must be upheld to ensure correct flow through the control valve Please note the flo...

Page 3: ...r the specific fitting for further details on proper installation Both inlet and return pipes are covered by a plastic or rubber protection cover which must be removed before installation After removing the protection cover make sure that the pipe is intact and unda maged especially at the pipe end as even small dents and scratches potentially pose a risk of leakage in the system Eventually deburr...

Page 4: ...rt must be inserted into the pipe always part of the delivery The copper insert should be placed inside the pipe on the beam Always support the copper pipe coil when inserting the copper insert into position Mount a compression coupling and or a valve to the pipe Don t stress the nut too much since this may crush the pipe Please refer to the suppliers manual 1 5 4 Flexible hoses Our flexible hoses...

Page 5: ...the label you ll find Order Order identification number Pos Order position Product Product configuration Project Project name Mark Marking noted on order Nozzles Number of nozzles Plugs Number of plugged nozzles Product ID Product number Sign To be signed when checked and commissioned on site 2 2 Measure air pressure and calculating the airflow Before calculating the airflow the static nozzle pres...

Page 6: ...ht to make changes without prior notice 2022 09 30 lindab for a better climate 2 2 2 Calculating the airflow After measuring the static nozzle pressure calculate the air flow per nozzle q 0 0622 P q air flow per nozzle P static nozzle pressure After finding the air flow per nozzle find the needed number of open nozzles q tot q n open q tot total air flow n open open nozzles Alternatively read off ...

Page 7: ...move the battery ocver plate Clean underneath the battery and inside the air dispersal duct with a vacuum cleaner and a piece of wet cloth Only use lukewarm water and a mild detergent 2 3 Changing the airflow Measure the static nozzle pressure Calculate the needed number of nozzles to be plugged in order to reach the desired airflow at the available air pressure as see the diagram above Plug or un...

Page 8: ...e follow the links below Building product declaration Declaration of conformity Eurovent certificate 4 3 Pressure class The waterborne products in Lindab active chilled beams battery products passive chilled beams battery and strips products facade units battery and radiant panels strips and panels are produced according to pressure class PN10 according to EN 1333 2006 This means the maximal worki...

Page 9: ... value of water must be between approximately 6 9 pH The water velocities should not exceed 1m s and should be kept as close to the nominal flow as possible to minimize noise and optimize the energy yield There should be used in line strainers to remove dirt particles from the water If the water contains any additive inhibitor this must be appropriate to use with copper and solder 4 5 Capacity tes...

Page 10: ...erefore made it our most important objective to contribute to an indoor climate that improves people s lives We do this by developing energy efficient ventilation solutions and durable building products We also aim to contribute to a better climate for our planet by working in a way that is sustainable for both people and the environment Lindab For a better climate For a better climate ...

Reviews: