Page 14
Calibration Procedure
• Insert one or two Intelligent Batteries into the PowerCenter.
-
The normal diagnostic tests are run and the LCD displays the
percent of charge in the battery.
• Momentarily press the “Mode Switch” to put the PowerCenter into
the battery calibration mode.
-
The ‘Charge’ LED is ON to indicate the battery is charging.
-
The LCD alternately displays ‘C 1’ and the percent of charge in the
battery.
-
The ‘C1’ display indicates the system is operating in the first of 3
phases of the calibration procedure.
-
The battery charges to maximum capacity.
• The PowerCenter automatically switches to discharge mode for the
second leg of the calibration operation.
-
The ‘RUN’ LED comes ON to indicate the battery is discharging.
-
The LCD alternately displays ‘C2’ and the percent of charge in the
battery.
-
The ‘C2’ display indicates the system is operating in the second
of 3 phases of the calibration procedure.
-
The battery is discharged to a known zero capacity level of 7.8 volts.
-
At this level, the battery has also been conditioned to correct or
prevent loss of capacity due to ‘Memory Effect’.
•The battery automatically begins charging to maximum capacity.
-
The ‘Charge’ LED comes ON.
-
The LCD screen alternately displays ‘C3’ and the percent of
charge in the battery.
-
The ‘C3’ display indicates the system is operating in the third of 3
phases of the calibration procedure.
-
The battery is fully charged and the indicated charge data stored
in the battery is updated to 100%.
-
The LCD alternately displays ‘Cb’ and the percent of charge in the
battery.
-
The code ‘Cb’ indicates calibration has been properly completed
on the first battery.