A-8
INSTALLATION
VANTAGE
®
600 SD
STANDBY POWER CONNECTIONS
The VANTAGE
®
600 SD is suitable for temporary, standby or
emergency power using the engine manufacturer’s recommended
maintenance schedule.
The VANTAGE
®
600 SD can be permanently installed as a standby
power unit for 240 volt-3 wire, 50 amp service. Connections must
be made by a licensed electrician who can determine how the
120/240 VAC power can be adapted to the particular installation
and comply with all applicable electrical codes. Refer to the con-
nection diagram shown in Figure A.4.
1. Install the double-pole, double-throw switch between the power
company meter and the premises disconnect. Switch rating
must be the same or greater than the customer’s premises dis-
connect and service over current protection.
2. Take necessary steps to assure load is limited to the capacity of
the VANTAGE
®
600 SD by installing a 50 amp, 240 VAC double
pole circuit breaker. Maximum rated load for each leg of the 240
VAC auxiliary is 50 amps. Loading above the rated output will
reduce output voltage below the allowable -10% of rated voltage
which may damage appliances or other motor-driven equipment
and may result in overheating of the VANTAGE
®
600 SD engine
and / or alternate windings.
3. Install a 50 amp 120/240 VAC plug (NEMA Type 14-50P) to the
double-pole circuit breaker using No. 6, 4 conductor cable of
the desired length.
4. Plug this cable into the 50 Amp 120/240 Volt receptacle on the
VANTAGE
®
600 SD case front.
240 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
50AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
FIGURE A.4 Connection of the VANTAGE® 600 SD to Premises Wiring
Summary of Contents for VANTAGE 600 SD
Page 19: ...A 12 NOTES VANTAGE 600 SD...
Page 36: ...B 17 NOTES VANTAGE 600 SD...
Page 39: ...C 3 NOTES VANTAGE 600 SD...
Page 44: ...D 5 NOTES VANTAGE 600 SD...
Page 49: ...E 5 NOTES VANTAGE 600 SD...
Page 51: ...F 2 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 52: ...F 3 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 53: ...F 4 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 54: ...F 5 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 55: ...F 6 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 56: ...F 7 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 57: ...F 8 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 58: ...F 9 CONNECTION DIAGRAMS VANTAGE 600 SD...
Page 64: ...Vantage 600 T4F 11981...
Page 65: ...ii THIS PAGE INTENTIONALLY LEFT BLANK...
Page 97: ...P 752 M jpg Covers 32 Vantage 600 T4F 11981 Printed 06 24 2016 at 13 37 16 Produced by Enigma...