Lincoln Electric RED-D-ARC GX 300 Operator'S Manual Download Page 14

A-6

INSTALLATION   

A-6

• Loose  connections  will  cause  the  output  termi-

nals  to  overheat.  The  terminals  may  eventually
melt.

• Do  not  cross  the  welding  cables  at  the  output

terminal  connection.  Keep  the  cables  isolated
and separate from one another.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power of the GX 300 consists of two 20
Amp-120 VAC (5-20R) duplex receptacles and one 50
Amp 120/240 VAC (14-50R) receptacle. The 240 VAC
receptacle  can  be  split  for  single  phase  120  VAC
operation.

The  auxiliary  power  capacity  is  10,000  watts  Peak,
9500 Watts Continuous of 60 Hz, single phase power.
The auxiliary power capacity rating in watts is equiva-
lent  to  volt-amperes  at  unity  power  factor.  The  max
permissible current of the 240 VAC output is 40 Amps.
The 240 VAC output can be split to provide two sepa-
rate 120 VAC outputs with a max permissible current
of  40  Amps  per  output  to  two  separate  120  VAC
branch  circuits  (these  circuits  cannot  be  paralleled).
Output voltage is within ± 10% at all loads up to rated
capacity.

The 120 V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs. The current
rating  of  any  plug  used  with  the  system  must  be  at
least  equal  to  the  current  capacity  of  the  associated
receptacle.

NOTE:

The 240 V receptacle has two 120 V circuits,

but are of opposite polarities and cannot be paralleled.

STANDBY POWER CONNECTIONS

The  GX  300  is  suitable  for  temporary,  standby  or
emergency  power  using  the  engine  manufacturer’s
recommended maintenance schedule.

The GX 300 can be permanently installed as a stand-
by  power  unit  for  240  VAC,  3  wire,  single  phase,  40
amp  service.  Connections  must  be  made  by  a
licensed  electrician  who  can  determine  how  the
120/240 VAC power can be adapted to the particular
installation  and  comply  with  all  applicable  electrical
codes.

• Install  the  double-pole,  double-throw  switch

between the power company meter and the premis-
es  disconnect.  Switch  rating  must  be  the  same  or
greater  than  the  customer’s  premises  disconnect
and service over current protection.

• Take  necessary  steps  to  assure  load  is  limited  to

the  capacity  of  the  GX  300  by  installing  a  40  amp,
240  VAC  double  pole  circuit  breaker.  Maximum
rated  load  for  each  leg  of  the  240  VAC  auxiliary  is
40  amperes.  Loading  above  the  rated  output  will
reduce output voltage below the allowable - 10% of
rated  voltage  which  may  damage  appliances  or
other  motor-driven  equipment  and  may  result  in
overheating of the GX 300 engine and/or alternator
windings.

• Install  a  50  amp,  120/240  VAC  plug  (NEMA  Type

14-50)  to  the  double-pole  circuit  breaker  using  No.
6, 4 conductor cable of the desired length. (The 50
amp, 120/240 VAC plug is available in the optional
K802R plug kit or as part number T12153-9.)

• Plug this cable into the 50 Amp, 120/240 Volt recep-

tacle on the GX 300 case front.

GX 300

CAUTION

Summary of Contents for RED-D-ARC GX 300

Page 1: ...th safety in mind However your overall safety can be increased by proper installation and thoughtful operation on your part DO NOT INSTALL OPERATE OR REPAIR THIS EQUIPMENT WITHOUT READING THIS MANUAL AND THE SAFETY PRECAUTIONS CONTAINED THROUGHOUT And most importantly think before you act and be careful For use with machines having Code Numbers 10851 North America s Largest Fleet of Welding Equipm...

Page 2: ...AKER WEARERS SHOULD CONSULT WITH THEIR DOCTOR BEFORE OPERATING Read and understand the following safety highlights For additional safety information it is strongly recommended that you purchase a copy of Safety in Welding Cutting ANSI Standard Z49 1 from the American Welding Society P O Box 351040 Miami Florida 33135 or CSA Standard W117 2 1974 A Free copy of Arc Welding Safety booklet E205 is ava...

Page 3: ...ctrical earth ground 3 f Maintain the electrode holder work clamp welding cable and welding machine in good safe operating condition Replace damaged insulation 3 g Never dip the electrode in water for cooling 3 h Never simultaneously touch electrically hot parts of electrode holders connected to two welders because voltage between the two can be the total of the open circuit voltage of both welder...

Page 4: ... prevent the welding sparks from starting a fire Remember that welding sparks and hot materials from welding can easily go through small cracks and openings to adjacent areas Avoid welding near hydraulic lines Have a fire extinguisher readily available 6 b Where compressed gases are to be used at the job site special precautions should be used to prevent hazardous situations Refer to Safety in Wel...

Page 5: ...riés et non inflammables 4 Des gouttes de laitier en fusion sont émises de l arc de soudage Se protéger avec des vêtements de protection libres de l huile tels que les gants en cuir chemise épaisse pan talons sans revers et chaussures montantes 5 Toujours porter des lunettes de sécurité dans la zone de soudage Utiliser des lunettes avec écrans lateraux dans les zones où l on pique le laitier 6 Elo...

Page 6: ...he information must be followed to avoid minor personal injury or damage to this equipment CAUTION Please Examine Carton and Equipment For Damage Immediately When this equipment is shipped title passes to the purchaser upon receipt by the carrier Consequently Claims for material damaged in shipment must be made by the purchaser against the transportation company at the time the shipment is receive...

Page 7: ...ion A 5 Auxiliary Power Receptacles and Plugs A 6 Standby Power Connections A 6 Premises Wiring A 7 Connection of Lincoln Electric Wire Feeders A 8 Operation Section B Safety Precautions B 1 General Description B 1 Design Features B 1 Engine Operation B 1 Fuel B 1 Welder Controls B 2 Engine Controls B 3 Starting and Stopping the Engine B 3 Stopping B 4 Welding Operation B 4 DC Stick Welding B 4 Co...

Page 8: ...r Filter Paper Element D 3 Spark Plug D 3 Spark Plug Service D 3 Fuel Filter D 4 Engine Adjustment D 4 Battery Maintenance D 4 Servicing Optional Spark Arrestor D 4 Welder Generator Maintenance D 5 Storage D 5 Cleaning D 5 Brush Removal and Replacement D 5 Troubleshooting Section E How to Use Troubleshooting Guide E 1 Troubleshooting Guide E 2 Troubleshooting Guide E 3 Troubleshooting Guide E 4 Tr...

Page 9: ...mm 1073 0 mm LUBRICATION VALVE LIFTERS FUEL SYSTEM GOVERNOR Full Pressure Hydraulic Mechanical Fuel Pump Mechanical Governor n o i t a l u g e R 5 r e t l i F w o l F l l u F h t i w AIR CLEANER ENGINE IDLER MUFFLER ENGINE PROTECTION Low noise Muffler Top outlet Shutdown on low oil Duel Element Automatic Idler can be rotated Made from pressure long life aluminized steel ENGINE WARRANTY 2 year unli...

Page 10: ...ECEPTACLES AUXILIARY POWER CIRCUIT BREAKER OTHER CIRCUIT BREAKERS 2 120VAC Duplex GFCI Two 20AMP for Two Duplex GFCI Recptacle 25AMP for Battery Charging Circuit 5 20R 1 120 240VAC Dual Two 50AMP for Dual Voltage 15AMP for 42V Wire Feeder Power Voltage Full KVA 14 50R ...

Page 11: ...e travel speed roughness of sur face on which the trailer will be operated environmental con ditions like maintenance 5 Conformance with federal state and local laws 1 1 Consult applicable federal state and local laws regarding specific requirements for use on public highways SAFETY PRECAUTIONS Only qualified personnel should install use or service this equipment LOCATION AND VENTILATION The welde...

Page 12: ...nnected Make certain that the RUN STOP switch is in the STOP position Remove the two screws from the rear battery tray using a screwdriver or a 3 8 socket Attach the negative battery cable to the negative battery terminal and tighten using a 1 2 socket or wrench NOTE This machine is furnished with a wet charged battery if unused for several months the battery may require a booster charge Be carefu...

Page 13: ...a metal water pipe going into the ground for at least ten feet and having no insulat ed joints or to the metal framework of a building which has been effectively grounded The U S National Electrical Code lists a number of alternate means of grounding electrical equipment A machine grounding stud marked with the symbol is provided on the front of the welder WELDING TERMINALS The GX 300 is equipped ...

Page 14: ...rcuits but are of opposite polarities and cannot be paralleled STANDBY POWER CONNECTIONS The GX 300 is suitable for temporary standby or emergency power using the engine manufacturer s recommended maintenance schedule The GX 300 can be permanently installed as a stand by power unit for 240 VAC 3 wire single phase 40 amp service Connections must be made by a licensed electrician who can determine h...

Page 15: ...0 50 AMP 120 240 VOLT RECEPTACLE CONNECTION OF GX 300 TO PREMISES WIRING WARNING Only a licensed certified trained electrician should install the machine to a premises or residential electrical system Be certain that The installation complies with the National Electrical Code and all other applicable electrical codes The premises is isolated and no feedback into the utility system can occur Certai...

Page 16: ...2 seconds unless welding is resumed If you are using an LN 25 without an internal con tactor the electrode will be energized when the GX 300 is started Connection of LN 7 or LN 8 to the GX 300 1 Shut the welder off 2 Connect the LN 7 or LN 8 per instructions on the appropriate connection diagram in Section F 3 Set the WIRE FEEDER VOLTMETER switch to either or as required by the electrode being use...

Page 17: ...ILIARY POWER Start the engine and set the IDLER control switch to the desired operating mode Full power is available regardless of the welding control settings providing no welding current is being drawn The auxiliary power of the GX 300 consists of two 20 Amp 120 VAC 5 20R duplex GFCI receptacles and one 50 Amp 120 240 VAC 14 50R receptacle The 240 VAC receptacle can be split for single phase 120...

Page 18: ...hese modes This control is not active in the TIG mode CC STICK PIPE modes In these modes the ARC CONTROL knob sets the short circuit current during stick welding arc force Increasing the number from 10 to 10 increases the short circuit current and prevents sticking of the electrode to the plate while welding This can also increase spatter It is recom mended that the ARC CONTROL be set to the minim...

Page 19: ... carburetor for quick starting 12 START PUSH BUTTON Energizes the starter motor to crank the engine 13 IDLER SWITCH Has two positions as follows 1 In the HIGH position the engine runs at the high idle speed controlled by the engine governor 2 In the AUTO position the idler operates as follows When switched from HIGH to AUTO or after start ing the engine the engine will operate at full speed for ap...

Page 20: ...tal and vertical up welding with all types of electrodes especially low hydrogen The out put CONTROL dial adjusts the full output range for stick welding The ARC CONTROL knob sets the short circuit cur rent during stick welding arc force Increasing the number from 10 to 10 increases the short circuit cur rent and prevents sticking of the electrode to the plate while welding This can also increase ...

Page 21: ...th an Amptrol or Arc Start Switch Set the MODE Switch to the TOUCH START TIG set ting Set the IDLER Switch to the AUTO position Set the WELDING TERMINALS switch to the REMOTELY CONTROLLED position This will keep the Solid State contactor open and provide a cold electrode until the Amptrol or Arc Start Switch is pressed When using the TIG Module the OUTPUT control on the GX 300 is used to set the m...

Page 22: ...ted capacity The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle NOTE The 240 V receptacle has two circuits each of which measure 120 V to neutral but are of opposite polariti...

Page 23: ...K1770 1 Undercarriages K1745 1 SINGLE GAS CYLINDER HOLDER For use on K1770 1 Undercarriage One or two may be installed on an undercarriage K1788 1 ROLL CAGE Gives added damage protection K886 2 CANVAS COVER Protects machine when not in use K1898 1 SPARK ARRESTOR Mounts inside exhaust pipe K702 ACCESSORY KIT Accessory set includes 35 ft 10 7 meters 2 AWG electrode cable 30 ft 9 1 meters 2 AWG work ...

Page 24: ...e end of each day s use refill the fuel tank to minimize moisture condensation in the tank Running out of fuel tends to draw dirt into the fuel system Also check the crankcase oil level and add oil if indicated WARNING ITEM MAKE AND PART NUMBER KOHLER CH22 ENGINE 4 1 6 3 H P m a r F 1 0 0 5 0 2 1 r e l h o K r e t l i F l i O Air Filter Element Kohler 4708303 Fram CA79 Air Filter Pre Cleaner Kohle...

Page 25: ...down a drain Oil Filter Change Drain the engine oil Remove the oil filter and drain the oil into a suitable container Discard the used oil filter Clean the filter mounting base and coat the gasket of the new oil filter with clean engine oil Screw on the new oil filter by hand until the gasket contacts the filter mounting base then use an oil fil ter socket tool to tighten the filter an additional ...

Page 26: ...d remains hot for a while after stopping the engine Be care ful not to touch the muffler while it is hot Spark Plug Service To ensure proper engine operation the spark plug must be properly gapped and free of deposits Remove the spark plug cap Clean any dirt from around the spark plug base Use a plug wrench to remove the spark plug Visually inspect the spark plug Discard them if the insulator is c...

Page 27: ... clean by wiping it with a damp cloth when dirty If the terminals appear corroded discon nect the battery cables and wash the terminals with an ammonia solution or a solution of 1 4 pound 0 1113 kg of baking soda and 1 quart 0 9461 of water Be sure the battery vent plugs if equipped are tight so that none of the solution enters the cells After cleaning flush the outside of the battery the bat tery...

Page 28: ...lip rings to wear and darken slightly Inspect the brushes when a generator over haul is necessary Do not attempt to polish slip rings while the engine is running WARNING Service and Repair should only be performed by Lincoln Electric Factory Trained Personnel Unauthorized repairs performed on this equip ment may result in danger to the technician and machine operator and will invalidate your facto...

Page 29: ...CAUSE lists the obvious external possibilities that may contribute to the machine symptom Step 3 RECOMMENDED COURSE OF ACTION This column provides a course of action for the Possible Cause generally it states to contact your local Lincoln Authorized Field Service Facility If you do not understand or are unable to perform the Recommended Course of Action safely contact your local Lincoln Authorized...

Page 30: ...nning 1 Contact your local Lincoln Authorized Field Service Facility 1 Battery is low Charge Battery 2 Loose battery cable connections Inspect clean and tighten 3 Faulty engine starter motor 4 Battery Circuit circuit breaker is tripped 1 Out of fuel Fill tank and bleed fuel system 2 Faulty fuel solenoid or faulty PC board or ignition system 1 Low oil level Change oil and oil filter and fill to pro...

Page 31: ... switch to Auto 2 External load on welder or auxil iary power Remove all external loads 3 Faulty PC board or idler sole noid 1 Poor work lead connection to work Make sure work clamp is tightly connected to clean base metal 2 Contactor switch is in wrong position Set to Welding On when welding without a control cable Refer to Operations chapter for prop er use of this switch 3 Faulty PC board Low i...

Page 32: ...s On position when welding without control cable 3 Faulty PC board or welder alterna tor 1 Poor remote control cable connec tion to 6 pin or 14 pin Amphenol connector Check connections 2 Faulty remote cable or faulty wire feeder or wire feeder cable Replace if necessary 3 Faulty control potentiometer or PC board 1 Wire Feeder Power circuit breaker open Check 42V and 120V beakers and reset if tripp...

Page 33: ...not stable or is not satis factory the engine runs normally The auxiliary power is normal 1 Make sure the MODE selector switch is in the correct position for the process being used For example CV WIRE PIPE CC STICK 2 Make sure the electrode wire gas voltage current etc is cor rect for the process being used 3 Check for loose or faulty connec tions at the weld output terminals and welding cable con...

Page 34: ...F 1 DIAGRAMS F 1 GX 300 ...

Page 35: ...F 2 DIAGRAMS F 2 GX 300 ...

Page 36: ...NCREASE OF THE HIGH IDLE ENGINE RPM BY CHANGING THE GOVERNOR SETTING OR OVERRIDING THE THROTTLE LINKAGE WILL CAUSE AN INCREASE IN THE AC WIRE FEEDER VOLTAGE WHICH CAN DAMAGE THE CONTROL CIRCUIT THE ENGINE GOVERNOR SETTING IS PRE SET AT THE FACTORY DO NOT ADJUST ABOVE RPM SPECIFICATIONS LISTED IN THE ENGINE WELDER OPERATING MANUAL N A WELDING CABLES MUST BE OF PROPER CAPACITY FOR THE CURRENT AND DU...

Page 37: ...F 4 DIAGRAMS F 4 GX 300 ...

Page 38: ...F 5 DIAGRAMS F 5 GX 300 ...

Page 39: ...F 6 DIAGRAMS F 6 GX 300 ...

Page 40: ...F 7 DIAGRAMS F 7 GX 300 ...

Page 41: ...F 8 DIAGRAMS F 8 GX 300 ...

Page 42: ...M IDLER CONTROL SHOWN IN AUTO POSITION S4 252 251 C3 800uf 150vdc POSITIVE BRUSH CONNECTED TO SLIP RING NEAREST TO THE LAMINATION WHITE TERM L2 L3 TWISTED PAIR W6 12 VOLT BATTERY GND H ENGINE BLOCK W11 LOCATED BELOW TERMINAL 2 S1RUN STOP SWITCH SHOWN IN RUN POS 12 7 6 1 1 2 6 10 L2 L3 RF CHOKES 16 9 8 1 CB8 TOP GND SCREW ON INSIDE OF CASE FRONT LEAD COLOR CODE B BLACK OR GRAY R RED OR PINK W WHITE...

Page 43: ... 10 20 80 A B CENTER OF GRAVITY WITH OIL IN ENGINE AND EMPTY FUEL TANK 29 88 33 62 36 24 10 28 10 78 TRUCK UNDERCARRIAGE MOUNTING HOLES 7 22 24 86 2 6 F 10 DIAGRAMS F 10 GX 300 DIMENSION PRINT GX 300 DIMENSION A DIMENSION B 23 50 16 75 ...

Page 44: ...GX 300 NOTES ...

Page 45: ...16 383 2259 and ask for the Welding School Registrar Lincoln Welding School BASIC COURSE 700 00 5 weeks of fundamentals There is a 10 discount on all orders of 50 00 or more for shipment at one time to one location Orders of 50 or less before discount or orders outside of North America must be prepaid with charge check or money order in U S Funds Only Prices include shipment by 4thClass Book Rate ...

Page 46: ...electrically live parts or electrode with skin or wet clothing Insulate yourself from work and ground No toque las partes o los electrodos bajo carga con la piel o ropa moja da Aislese del trabajo y de la tierra Ne laissez ni la peau ni des vête ments mouillés entrer en contact avec des pièces sous tension Isolez vous du travail et de la terre Berühren Sie keine stromführenden Teile oder Elektrode...

Page 47: ...gute Be und Entlüftung des Arbeitsplatzes Mantenha seu rosto da fumaça Use ventilação e exhaustão para remover fumo da zona respiratória Turn power off before servicing Desconectar el cable de ali mentación de poder de la máquina antes de iniciar cualquier servicio Débranchez le courant avant l entre tien Strom vor Wartungsarbeiten abschalten Netzstrom völlig öff nen Maschine anhalten Não opere co...

Page 48: ...s and Service through Subsidiaries and Distributors Worldwide Cleveland Ohio 44117 1199 U S A TEL 216 481 8100 FAX 216 486 1751 WEB SITE www lincolnelectric com World s Leader in Welding and Cutting Products ...

Reviews: