Features of the automatic system include an adjustable line regulator, hoses with built-in check valves, gas economizer circuit , system status lights and wall mounting brackets. 

3. Description

 

The Model 240 Series Switchover Manifolds are designed to provide a continuous supply of gas. The system automatically changes from a depleted bank of cylinder(s) in service to 
a full reserve bank without an interruption of gas supply. A simple rotation of the primary bank selector knob resets the unit once the depleted bank of cylinder(s) has been replaced. 
The standard outlet regulator maintains a constant line pressure, even during the switchover process. Built-in economizer circuit insures that any gas pressure build-up on the 
reserve side will not vent to atmosphere, but will be diverted into the gas stream where it can be used.

 

4.  General Instructions

 

Manifolds should be installed in accordance with guidelines stated by the National Fire Protection Association, the Compressed Gas Association, OSHA and all applicable local codes. 
The manifolds should not be placed in a location where the temperature will exceed 120°F (49°C) or fall below –20°F (-29°C) for sustained periods of time. 

A manifold placed 

outside in an open location should be protected against rain and excessive moisture. During winter, protect the manifold from ice and snow. The manifold should 

be located in a clean, well-ventilated area which is free of oil and combustible materials.

Leave all protective covers in place until their removal is required for installation. This precaution will keep moisture and debris from the piping interior, avoiding operational problems.

All safety relief valves should be piped/vented to an outside location away from personnel. Failure to properly pipe away the external manifold relief valve can create hazardous 
conditions. Flammable, oxidizing and asphyxiant gases in the general vicinity of personnel can result in extremely hazardous conditions. Any failure of internal pressure reducing valves, 
seats or seals can cause excess pressure to build up and release dangerous gases into the surrounding environment.

5.  Design Specifications

 

Maximum Inlet Pressure 

240 – 235 psig 

  

 

240HP – 350 psig 

  

Operating Temperature 

-20 degrees F to +120 degrees F

 

Pressure Gauge Size 

2” Dial 

 

Inlet Connection 

½” FNPT Port 

 

Outlet Connection 

½” FNPT Port

 

Alarm 

Integral alarm, Optional Remote Alarm 

 

 Available 

 

Header 

½” Nominal Pipe Size 

 

Power Requirements 

Manifold Box: 120 VAC, 1.25 Amps.

 

Flexible Hose Length 

72 inches unless otherwise specified

  

6. Standard Factory Pressure Settings

  

Inlet Pressure Gauge  

240 – 400 psi 

 

240HP – 600 psi

  

Outlet Pressure Gauge 

240 – 200 psi 

 

240HP – 400 psi

  

Outlet Pressure Range 

240 – 20 to100 psig 

240HP – 40 to 180 psig

  

Switchover Pressure 

240 – 140 psig   

240HP – 240 psig

  

Alarm Set Point 

240 – 150 psig   

240HP – 250 psig

  

7. Nameplate

  Each control box includes a nameplate with the following information.
 
•  Part Number and Gas Service
•  Model Number
•  Pressure Ratings
• Connections
•  Relief Valve Rating
•  Manufacturing Date Code 
•  Any Electrical requirements
 

 

8. Installation Instructions

NOTE: A detailed video of a typical installation can be viewed at

 -

 http://bit.ly/S4BUgV

The Series 240 Manifolds can be used either with two cylinders (one on each side) or with multiple cylinders on each side. All systems will come with a multi-port adapter for connection 
of up to 3 cylinders per side. See Figure 1. Ports that are not used must be plugged. All plugs must be sealed with Teflon tape and wrench tightened.

THE HARRIS PRODUCTS GROUP

www.harrisproductsgroup.com

1.800.241.0804

Summary of Contents for 4301530

Page 1: ...ere and in an area away from personnel Be sure that venting and disposal methods are in accordance with Federal State Provincial and local requirements Locate and construct vent lines to prevent conde...

Page 2: ...be piped vented to an outside location away from personnel Failure to properly pipe away the external manifold relief valve can create hazardous conditions Flammable oxidizing and asphyxiant gases in...

Page 3: ...he control box to the central piping system Common 1 11 NPS manifold fittings are supplied with this system Other connections may be used The outlet port connection on the control box is FNPT 5 It is...

Page 4: ...are found they must be eliminated before proceeding Attempt to re tighten connections with a wrench until the leakage stops If leakage cannot be stopped do not use the manifold Contact The Harris Prod...

Page 5: ...eam piping system Check for leaks at all joints and connections Retighten repair or replace piping or fittings Leakage at cylinder valve Check for leaks at cylinder connection and valve Replace cylind...

Page 6: ...saci n y la acumulaci n de gas Aseg rese de que la salida de ventilaci n no est obstruida por lluvia nieve hielo insectos aves etc No interconecte las l neas de ventilaci n si se necesita m s de una v...

Page 7: ...terna lejos del personal No colocar hacia afuera adecuadamente la v lvula de escape del colector puede provocar condiciones peligrosas Los gases inflamables oxidantes y asfixiantes en la cercan a gene...

Page 8: ...l Los accesorios comunes del colector de NPS 1 in 11 se suministran con este sistema Se pueden utilizar otras conexiones La conexi n del puerto de salida en la caja de control es de in FNPT 5 Se recom...

Page 9: ...iltraciones Si se encuentran filtraciones deben eliminarse antes de proceder Trate de reajustar las conexiones con una llave hasta que la filtraci n se detenga Si no se puede detener una filtraci n no...

Page 10: ...si hay filtraciones en la conexi n del cilindro y la v lvula reemplace el cilindro Filtraciones del regulador Verifique si hay filtraciones en las conexiones del regulador reemplace las conexiones y...

Page 11: ...z Assurez vous que la sortie d vacuation ne peut tre obstru e par de la pluie de la neige de la glace des insectes des oiseaux etc Ne connectez pas des conduites d vacuation entre elles Si plusieurs v...

Page 12: ...l ext rieur dans un endroit loign du personnel Ne pas correctement acheminer la soupape de s curit du collecteur externe par canalisation constitue un danger La pr sence de gaz inflammable oxydant et...

Page 13: ...tandard du collecteur 1 po 11 NPS sont fournis avec ce syst me D autres raccords peuvent tre utilis s L orifice de raccordement de sortie du bo tier de contr le est un FNPT de po 5 Il est recommand d...

Page 14: ...fuites En cas de fuites celles ci doivent tre r par es avant de continuer Essayez de resserrer les raccords l aide d une clef jusqu arr ter la fuite Si la fuite ne peut pas tre arr t e n utilisez pas...

Page 15: ...es au niveau du d tendeur V rifiez que les raccords du d tendeur ne pr sentent pas de fuites Remplacez les raccords ou le d tendeur Le r glage du d tendeur de conduite est trop lev R glez la pression...

Page 16: ...9504139 REV A 062013 THE HARRIS PRODUCTS GROUP www harrisproductsgroup com 1 800 241 0804...

Reviews: