IS212 ECN3592
7
1.5
PRESSURE SETTING
Pressure setting can be carried out by the removal of the facia panel. This procedure is to expose the test
nipple.
With all burners lit and set to maximum, ensure that the supply pressure for Natural gas appliances is
20mbar and the burner pressure is adjusted to 16mbar. For Propane appliances ensure the supply pressure
is set to 37mbar and the burner pressure is set to 25mbar.
Pressure measurement is via the test nipple at the end of the manifold rail. Note: To obtain the above
burner pressures adjust the regulator as supplied with unit. When correct operating pressures are
obtained, re-assemble the unit.
1.6
HEAT INPUT
The total nominal gross heat input for the appliances with both burners in full operation are as follows: -
GS4/N Natural gas
5.4 kW
GS4/P Propane gas
5.5 kW
GS7/N Natural gas
7.5 kW
GS7/P Propane gas
8.0 kW